PowerWizard 1.0 & 2.0 Control Systems User Manual
CHANGING SCADA PASSWORD (PowerWizard 2.0 only) – used to set-up, change or disable a SCADA password.
Highlight and press enter to proceed to the password entry screen. To set-up or change the password, enter the new
password using the cursor keys. Passwords may be 16 digits long. To disable the SCADA security password, set the
password to '0'. Press the Enter key to save.
4.4

Real Time Clock Programming (PowerWizard 2.0)

The real time clock provides information for the time and date of an automatic time based start/stop control. It also
provides a mechanism for time stamps in the event log. The real time clock is not calibrated and is for information
only. The date and time are set by the user.
1. In order to set the time or date format:
MAIN MENU > CONFIGURE > TIME/DATE
2. To set the time, highlight the time then press the Enter key twice.
3. Use the cursor keys to set the time and press the Enter key to save. Press the Escape key to return.
4. To set the date, highlight the date then press the Enter key twice.
5. Use the cursor keys to set the date and press the Enter key to save. Press the Escape key to return.
6. To set the date format, highlight either the FORMAT DD/MM/YY or FORMAT MM/DD/YY and press the Enter key.
7. Use the cursor keys to select the required date format and press the Enter key to save.
4.5
Fuel Priming – Engines with Electronic Fuel Lift Pump
Certain engines fitted with an electronic fuel pump do not have a manual-priming feature on the engine. In these
circumstances the PowerWizard can be used to energise the fuel lift pump in order to prime the engine.
1. In order to prime the generating set:
MAIN MENU > CONTROL > ENGINE FUEL PRIMING
2. To prime the set press the right cursor key, this will initiate a 180 second priming cycle.
3. To exit the priming cycle press the left cursor key.
Note – The generating set may only be primed when the set is stopped and there are no active or present shutdown
conditions.
4.6
Programmable Cycle Timer (PCT) (PowerWizard 2.0)
The Programmable Cycle Timer (PCT) feature, if installed, allows the operator to program times when two independent
tasks, called PCT outputs, will be activated or deactivated automatically during the week. If you require this
functionality and it is not installed on your generating set, please contact your supplying dealer.
This is useful for cases where two or more generating sets are required to automatically share the duty of supplying a
load throughout the week. Using programmable cycle timer, each generating set can be programmed to start and stop
at pre-set times. The co-operation of a transfer switch is required to ensure that the generating sets are not stopped on
load.
Programmable Cycle Timer can also be used in cases where a standby set does not have access to a utility supply to
power a trickle charger. Programmable Cycle Timer can be used to run the set for an hour a week to keep the battery
charged.
16