DESCRIPTION
The Q7751A Router doubles the bus length and the number
®
of nodes on the L
W
ON
ORKS
Q7751A2010 has an FTT-10 transceiver and is used on
L
W
networks with the Excel 10 series 2000 family of
ON
ORKS
controllers. The Q7751A1012 has a TP-78 transceiver and is
used on L
W
networks with the Excel 10 VAV1 series
ON
ORKS
1000 controllers.
The Q7751A is a two-piece design allowing pre-wiring and
cable testing prior to installing the router. The front panel
includes a printed circuit board (PCB) with active electronics.
It also has a service switch and two service LEDs; a
combination power/wink LED, an activity LED and two
network connectors. See Fig. 1 for front panel view.
B
SERVICE
LEDs
CHANNEL A
CHANNEL B
B A
SERVICE
SWITCH
PACKET ACTIVITY LED ROUTER
TRANSFERRING PACKETS: FLASHING
1
OUTLET ACCESS JACKS; USE FOR ACCESS TO L
2
ROUTER INTERFACE MODEL AND SOFTWARE REVISION NUMBERS.
3
PEEL-OFF CODE 39 FORMAT BAR CODE OF ROUTER INTERFACE
Neuron
®
CHIP ID NUMBER.
Fig. 1. Q7751A Router front plate.
®U.S. Registered Trademark
Copyright © 1999 Honeywell Inc. • All Rights Reserved
(E-Bus) network. The
A
1
1
2
LPR-10
U
U
L
L
3
3
POWER LED:
POWER ON: ILLUMINATED
CONTINUOUSLY
W
BUS.
ON
ORKS
M16383
Q7751A Routers
The router is installed in a Type 2 base plate. Wiring
connections are presented in Table 1. Specifications for the
router are shown in Table 2. Network and power are
connected to screw terminals located on a Type 2 base plate.
The router is plugged into the base plate. No wiring is ever
connected directly to the router. A writing space is provided
on the back of the base plate for recording the date of
installation and other important information. See Fig. 2 for
front view of base plate. See Fig. 3 for rear view of base
plate.
3
1
TEST
POINTS
INTERFACE
CONNECTOR
2
1
THREADED SCREW HOLES FOR ATTACHING ROUTER INTERFACE TO
BASE PLATE. USE 8-32, 3/8 IN. SCREW, Echelon 205-0130-01 OR EQUAL.
2
0.230 IN. HOLES FOR ATTACHING BASE PLATE TO ELECTRICAL BACK
BOX OR SUB-PANEL.
3
0.180 X 0.280 IN. HOLE FOR THE ATTACHING BASE PLATE TO
ELECTRICAL BACK BOX OR SUB-PANEL. USE 6-32, FLAT-HEAD,
3/8 IN. MINIMUM SCREW.
Fig. 2. Q7751A front view of base plate.
2
B
A
2
1
M16381
95-7510-3

Advertisement

loading

Summary of Contents for Honeywell Q7751A

  • Page 1 Table 1. Specifications for the router are shown in Table 2. Network and power are The Q7751A Router doubles the bus length and the number connected to screw terminals located on a Type 2 base plate.
  • Page 2 WRITING SPACE FOR INSTALLER. USE FINE POINT M16382 SANFORD SHARPIE MODEL 30001 OR EQUAL. Fig. 3. Q7751A rear view of base plate. The Type 2 base plate is keyed to prevent accidental insertion of an incorrect module. The router is attached to the base plate with two 8-32 x 3/8 in.
  • Page 3: Installing The Router

    Q7751A ROUTERS Table 1. Router Wiring Connections. Screw Terminal Wiring Connection 1 and 2 Incoming network wiring, polarity insensitive; CHANNEL A. 3 and 4 Outgoing network wiring, polarity-insensitive; CHANNEL A. 5 and 14 Cable shields; terminals 5 and 14 are internally connected.
  • Page 4 Q7751A ROUTERS TROUBLESHOOTING Table 3 contains common troubleshooting symptoms and possible reasons and actions for repair. Table 3. Troubleshooting symptoms and solutions. Symptom Diagnosis Power LED lit This is the normal LED state with node powered. Power LED unlit Power supply that provides power to the module has lost primary power. Check power supply outlet for power.