&DEOH FRQQHFWLRQ LQ WUDQVIRUPHU SDQHO
Fig. 19:
NOTE!
Connecting
high-voltage cables
832-6008.0 * INSTALLATION SIMOSEC * REVISION 02
9.4
Connecting transformer panel to high voltage
$V IRU WKH H[DFW SDQHO GLPHQVLRQV VXFK DV HJ WKH FDEOH FRQQHFWLRQ KHLJKW SOHDVH UHIHU
WR WKH UHOHYDQW GLPHQVLRQ GUDZLQJ DQG DUUDQJHPHQW GLDJUDP
8VH FDEOH VHDOLQJ HQGV ZLWK D PD[LPXP FDEOH OXJ ZLGWK RI PP
Õ
5HPRYH DGKHVLYH ODEHO IURP SRLQW RI FDEOH FRQQHFWLRQ
Õ
5HPRYH EROW FRYHU ! N9
Õ
%ROW FDEOH OXJ DQG SRLQW RI FDEOH FRQQHFWLRQ WRJHWKHU WLJKWO\ DQG IUHH IURP GLVWRUWLRQV
DQG JDSV
7KH WLJKWHQLQJ WRUTXH DW WKH SRLQW RI FDEOH FRQQHFWLRQ LV 1P $V IRU WKH WLJKWHQLQJ
WRUTXHV RI WKH FDEOH OXJV FDEOH VHDOLQJ HQGV SOHDVH REVHUYH WKH PDQXIDFWXUHUnV
LQVWUXFWLRQV
Õ
+DQJ WKH EROW FRYHU ! N9 LQ RYHU WKH SRLQW RI FDEOH FRQQHFWLRQ
a
Bolt cover (> 17.5 kV)
s
Cable sealing end
d
Upper fuse contact
f
HV HRC fuse link
g
Lower fuse contact
h
Earthing point of cable shields
j
Bolted joint at point of cable connection /
cable lug with adhesive label to prevent the
bolt cover from falling out
k
Post insulator
l
Earthing switch contact
,QVWDOODWLRQ
25