Instructions for installation, setup and operation - FP9000L-2/4/6/8 CONTENTS: INTRODUCTION TECHNICAL PARAMETERS CONTROLS AND INDICATION FACTORY SET PARAMETERS INSTALLATION AND PANEL SETUP LEVELS OF ACCESS PANEL CONDITIONS CONDITIONS FOR USE, STORAGE AND TRANSPORT CONTENT AND COMPLEX OF DELIVERY WARRANTY Page 2 of 16...
Instructions for installation, setup and operation - FP9000L-2/4/6/8 1. INTRODUCTION FP9000L-2/4/6/8 is a conventional Fire alarm panel with 2, 4, 6 or 8 lines. Certified to standards EN 54-2 and EN 54-4. Each line can be connected to 32 detectors. The panel has 4 relay outputs, 2 of which are controllable and one relay.
Page 4
Instructions for installation, setup and operation - FP9000L-2/4/6/8 3А/125V AC, Electrical characteristics 3A/30V DC Independent relay output in case of failure: Quantity potentional-free, Type NC / NO switching 3А/125V AC, Electrical characteristics 3A/30V DC Delay outputs: ...
Instructions for installation, setup and operation - FP9000L-2/4/6/8 interruption) and automatic reset; Ability to delay controllable and general outputs for fire for a period of 0 to 7 minutes after the registration of state Fire,with DIP switch.; Built-in sounder in case of fire – monotonal, continuous with the possibility of exclusion; ...
Page 6
Instructions for installation, setup and operation - FP9000L-2/4/6/8 When in Disabled component / line or controllable output / a steady yellow “DISABLE” light will light up. Illuminates with steady yellow light at short or interruption of output devices “OUTS” power supply line “DEL OUTS”...
Page 7
Instructions for installation, setup and operation - FP9000L-2/4/6/8 Keyboard entry mode: - Changing the access level; Information and Levels 1 - Disable mode; management and 2 - Test mode. Keyboard entry mode: Information and Levels 1 - Changing the access level. - Disable mode management and 2...
Page 8
Instructions for installation, setup and operation - FP9000L-2/4/6/8 Fig.1 One line can allow the installation of up to 32 Fire detectors generally, regardless of their type. To the unused lines, directly to the terminals mount the final element "EOL", otherwise the lines will be able in Fault condition.
Page 9
Instructions for installation, setup and operation - FP9000L-2/4/6/8 Delay Outputs In the panel can be set to delay outputs with DIP switch on Level 3. DIP-4 123S 000X - without delay outputs 001X - 1 minute delay 010X - 2 minute delay 011X - 3 minute delay 100X - 4 minute delay 101X - 5 minute delay...
Page 10
Instructions for installation, setup and operation - FP9000L-2/4/6/8 Fig. 3 If controllable outputs are not used, directly to terminals "+Outx", "-Outx" a resistor 4,7k/0,5W is connected, otherwise the outputs will be in Fault condition. 5.3.2. Installation of the executive devices to RELAY OUTPUTS. Used: Terminal "+28VDC"...
Instructions for installation, setup and operation - FP9000L-2/4/6/8 FIRE/C" and "REL FIRE/NC " and in case of Fire - between terminals "REL FIRE/C" and "REL FIRE/NO ". If relay outputs are not used, then its terminals remain free (nothing is connected to them). 5.4.
Page 12
Instructions for installation, setup and operation - FP9000L-2/4/6/8 In access level 2 are available are following features: Exit from Fire condition; suppression of the outputs, activated when Fire; involuntary activation of the controllable outputs; suppression of built- in sounder. Switching from Level 2 to Level 1 and vice versa happens after a combination of buttons and the relevant information on the led indicator "Level Access".
Page 13
Instructions for installation, setup and operation - FP9000L-2/4/6/8 Beeper indication - Sounder is constantly on. Active buttons button "BUZZER SILENCE". Pressing it leads to: - Disabling the embedded sounder, if it has responded to Fire or Fault; - Activating the built-in sounder, if the panel is in Fire or Fault condition and the tale is disabled by previous pressing of the same button.
Page 14
Instructions for installation, setup and operation - FP9000L-2/4/6/8 Beeper indication – The built-in sounder is activated with a discontinuous signal. Active buttons button "BUZZER SILENCE". Pressing it leads to: - disabling the embedded sounder, if it is activated by Fire or Fault; - activating the built- in sounder, if the panel is in Fire or Fault condition and the annunciator is disabled by previous pressing the same button.
Instructions for installation, setup and operation - FP9000L-2/4/6/8 LED indication - light up indicators: - "TEST" is lit with yellow light - " 1 2 3 4 5 6 7 8 " local line indicator in Test lights up with flashing yellow and red light. ...
Page 16
Instructions for installation, setup and operation - FP9000L-2/4/6/8 the startup has been done by authorized persons; The requirements for operation conditioned in this instruction were met; Defects are not caused by natural phenomena and accidents of thr plug socket. DMTeh wishes you splendid work! For any questions may contact the company's technical staff DMTeh, by email.