Navien NFC-175 Service Manual page 51

Nfc condensing boilers
Table of Contents

Advertisement

Point
Function
Exhaust Thermistor
Heating Return
Temperature Sensor
Heating Supply
A
Temperature Sensor
High
Temperature Limit Switch
APS
B
Outdoor Thermostat
Flame Rod
C
Ground Wire
Water Pressure Sensor
D
Gas Valve
Dual Venturi
E
Igniter
F
Power Input
G
Fan Motor
Version 1.0
CN No.
Wire Color
CNJ1 1-2
BLUE-BLUE
CNJ1 5-6
BLUE-BLUE
CNJ1 7-8
BLUE-BLUE
CNJ1 13-14
BLACK-BLACK
CNJ1 9-10-12
RED-BLACK-WHITE
CNT3
BLUE-BLUE
CNI1 2
BLACK
CNI1 1
GREEN / YELLOW
CNG1 4-5-6
RED-BLACK
CNG1 2-3
WHITE-YELLOW
CNG1 1-2
WHITE-RED
CNO1 1-2-4
BROWN-BLACK-BLUE
CNO1 5-7
BLUE-BROWN
CON1 1-2
WHITE-BLACK
CNR1 4-7
BLACK-RED
CNR1 2-4
BLACK-YELLOW
CNR1 3-4
BLACK-ORANGE
CNR1 1-4
BLACK-WHITE
Normal Value
Voltage changes according to
DC 0-5V
temperature
Voltage changes according to
DC 0-5V
temperature
Voltage changes according to
DC 0-5V
temperature
DC 0V
Normally Shorted. Confirm RMS voltage
DC 5V
Voltage changes according to
DC 0-5V
temperature
Measure the current when the burner is
DC 10uA
operating.
Check for properly grounded wire
DC 0-5V
Confirm voltage as the Main Gas Valve 1
DC 22-24V
is operating.
Confirm voltage as the Main Gas Valve 2
DC 22-24V
is operating.
ON : AC 95-120V
Confirm voltage relative to operation
OFF : 0V
ON : AC 97-138V
Confirm voltage when the unit is
OFF : 0V
igniting.
Confirm appropriate power source.
AC 97-138V
Confirm the fuse.
Confirm the circuit breaker
DC 127-184V
Confirm steady voltage
DC 15V
Confirm steady voltage
Voltage changes relative to fan
DC 0-7.5V
operation
0-6,700rpm
Check pulse
Check
NFC Service Manual
51

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nfc-200

Table of Contents