2002 Hoover St. • Cordele, Georgia 31015 (229) 273-9558 • Fax (229) 273-5154 E-mail: icesales@airxcel.com • Internet: www.acice.com The most current version of this manual can be found at www.acice.com. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2 Part Number 01706...
How To Use This Manual This manual is intended to be a guide to Industrial Climate Engineering's line of vertical air conditioners. It contains installation, troubleshooting, maintenance, warranty, and application information. The information contained in this manual is to be used by the installer as a guide only. This manual does not supersede or circumvent any applicable national or local codes.
B = February F = June K = October E = 2015 C = March G = July L = November F = 2016 D = April H = August M = December ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
Heating Mode: A wall-mounted thermostat controls the heating cycle of models which incorporate resistance heating elements. On a call for heat, the thermostat closes the heat relay to energize the indoor blower and the resistance elements. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
Switch closure and fan operation occurs when the pressure reaches 400 PSIG. The switch opens again when the refrigerant pressure falls to 245 PSIG. Therefore, the outdoor fan always starts after the compressor, and it will cycle frequently during normal operation at low outdoor conditions. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
The units are designed to operate when either the left or right side (not both) on the condenser section are blocked. The open side and the top should have a minimum clearance of 24". The rear of the unit should be 60" from any obstruction to air flow. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
Extension length should be cut flush with the inside wall for applications without duct work. Applications using duct work should be designed and installed in accordance with all applicable safety codes and standards. ICE strongly recommends referring to the current editions of the National Fire ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
2. The SlimPac™ ECUA is shipped with the bottom brackets easily removed. 3. Refer to Figure 3. Attach the bottom support bracket to the wall using appropriate hardware. Figure 4. Wall Mounting Detail ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
The power supply(s) should have the proper voltage, phase, and ampacity for the selected models. Low Voltage (Control) Wiring 1. Mount the sub-base on a level plane. Use a line and surface level. Connect the thermostat wire as shown in Figure 4. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
"R" terminal on the thermostat. This will disable the 24V control voltage. See Figure 4. NOTE: THE INTERNAL TRANSFORMER IS NOT DESIGNED TO POWER OTHER EXTERNAL DEVICES. Figure 5. Thermostat Wiring Diagram ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
2. Set the system to operate in the heating mode as described in section 3.2 above. Trigger the normally closed external device to open and the ECUA should shut off. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
4. Unit off on high or low pressure limit. 4. Reset pressure switch. 5. Internal component or connection 5. Check for loose wiring. Check components for failure. failure. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
1. Start-Up Voltage: Measure the voltage at the compressor contactor during start-up. The voltage must exceed the minimum shown in Table 5, section 2.2, or compressor failure is likely. A low voltage condition must be corrected. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
Page 23
A short circuit at high voltages indicates a motor defect. Do not do this test under vacuum. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
Chapter 5 Maintenance Scheduled Maintenance Industrial Climate Engineering strongly recommends that the air conditioner be serviced a minimum of twice a year – once prior to the heating season and once prior to the cooling season. At this time the filters, evaporator coil, condenser coil, the cabinet, and condensate drains should be serviced as described below.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE-TO-STATE. Some states do not allow limitations or exclusions, so the above limitations and exclusions may not apply to you. 06/2018 Rev.7 ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...
Service and Parts in the menu on the left hand side of the Home page. From the drop down menu, select Exploded Views. Once here, you can select your air conditioner or heat pump. The units are grouped by model and by the refrigerant – R-22 or R-410A. ICE SlimPac ECUA12-18 I&O Manual 03/2019 Rev.2...