Technical specifications
A.1 General specifications
Environmental Conditions - Operating
Ambient temperature range
(Inlet Air 25 mm below unit)
Atmospheric pressure
Concentration of contaminants
EN 60068-2-14, Test Nb, temperature
change
EN 60068-2-27 Mechanical shock
EN 60068-2-6 Sinusoidal vibration
High Potential Isolation Test
24 V/5 V nominal circuits
115/230 V circuits to ground
115/230 V circuits to 115/230 V circuits
115 V/230V circuits to 24 V/5 V circuits
Protection Class: Protection Class II according to EN 61131-2 (Protective conductor not
required)
Degree of protection
● IP20 Mechanical Protection, EN 60529
● Protects against finger contact with high voltage as tested by standard probe. External
Rated voltages
Rated Voltage
24 VDC
120/230 VAC
NOTICE
When a mechanical contact turns on output power to the S7-1200 CPU, or any digital
signal module, it sends a "1" signal to the digital outputs for approximately 50
microseconds. You must plan for this, especially if you are using devices which respond to
short duration pulses.
98
protection required for dust, dirt, water and foreign objects of < 12.5mm in diameter.
0° C to 55° C horizontal mounting
0° C to 45° C vertical mounting
95% non-condensing humidity
1080 to 795 hPa (Corresponding to an altitude of -1000
to 2000m)
S0
: < 0.5 ppm; H
2
condensing
5° C to 55°, 3° C/minute
15 G, 11 ms pulse, 6 shocks in each of 3 axis
DIN rail mount: 3.5mm from 5-9 Hz, 1G from 9 - 150 Hz
Panel Mount: 7.00mm from 5-9 Hz, 2G from 9 to 150 Hz
10 sweeps each axis, 1 octave per minute
520 VDC (type test of optical isolation boundaries)
1,500 VAC routine test/1950 VDC type test
1,500 VAC routine test/1950 VDC type test
1,500 VAC routine test/3250 VDC type test
Tolerance
20.4 VDC to 28.8 VDC
85 VAC to 264 VAC, 47 to 63 Hz
S: < 0.1 ppm; RH < 60% non-
2
Manual, 11/2009, A5E02486774-01