Rear Panel - Tripp Lite SmartOnline SU3000RTXL2U Owner's Manual

Rack/tower on-line ups system
Hide thumbs Also See for SmartOnline SU3000RTXL2U:
Table of Contents

Advertisement

Available languages

Available languages

5. Operation
"BATT LOW" LED: This yellow LED will illuminate when the UPS system's
battery charge level is low. The UPS alarm will beep until the batteries are
either depleted or adequately recharged.
"ON BATT" LED: This green LED will illuminate continuously to indicate AC
line voltage is absent (or out of range) and the UPS system is providing
equipment with battery-derived AC power. The UPS system will also beep
every 2 seconds (unless silenced by the "ON/TEST" button) and the % level
LEDs (25%, 50%, 75%, 100%) will display the battery charge level.
"REPLACE BATT" LED: This red LED as well as the red "FAULT" LED will
illuminate continuously and the UPS alarm will beep every 2 seconds if the
UPS system fails the automatic self-test. Allow the UPS system to charge
for at least 12 hours and perform a self-test as described in Section 5.1:
Front Panel Switches. If the condition persists, contact Tripp Lite.

5.5 Rear Panel

Accessory Card Slot: Remove the cover panel from this slot to install an
optional internal WEBCARDLX accessory, sold separately. WEBCARDLX
provides a network interface for monitoring and control via SNMP , Web,
SSH or telnet, enabling remote reboots, shutdowns and more.
External Battery Pack Connector
Output Circuit Breakers: These resettable circuit breakers protect the UPS
system from output overload. If a breaker trips, remove some of the load
on the circuit and allow the UPS system to cool before pressing the breaker
button to reset.
Input Power Cord: This permanently attached power cord connects the
UPS system to a compatible power outlet.
NEMA L5-30P
13
17-04-276 9335AA.indb 13
5/1/2017 1:24:48 PM