Model Range - Kohler PowerWAVE 9500DPA User Manual

(100–500 kva/kw) parallelable up to 3 mva/mw
Table of Contents

Advertisement

:
2.2

Model range

As described previously, the PowerWAVE 9500DPA UPS cabinet can house up to five 100 kW UPS modules, so each
cabinet can be rated up to 500 kW in 100 kW increments.
Active sub-module
Passive sub-module
Each UPS module comprises two sub-modules; one is known as the 'Active' sub-module and the other as the 'Passive'
sub-module. These are mounted in the UPS cabinet in pairs, with the Active sub-module located on top of the Passive
sub-module. The first module to be installed in the cabinet must be fitted to the bottom position with subsequent modules
fitted in the next lowest available slot. When it is installed in the cabinet, each module is assigned an ID number to allow it
to be identified by the system control logic for purposes such as monitoring and event logging. The modules fitted in the
first cabinet should be identified as illustrated in Figure 2.1. In a multi-cabinet installation, the modules in the second
cabinet are given an identity '06' to '10', those in the third cabinet are given '11' to '15', and so on.
The following table shows the static parameters for each configuration.
System power rating (per cabinet) (kVA/kW)
Cabinet weight including modules (kg)
Cabinet weight without fitted modules (kg)
Cabinet dimensions (w x h x d) mm
Heat dissipation 100% linear load (W)
Heat dissipation 100% linear load (BTU)
Heat dissipation 100% non-linear load (W)
Heat dissipation 100% non-linear load (BTU)
Heat dissipation no load (W))
Acoustic noise (@ 100% / 50% load)
Cooling airflow (25°C - 30°C) at full load (m³/s)
Installation clearances (mm)
UPS Module weight
UPS Module dimensions (w x h x d) mm
4
UPS Module 05
UPS Module
UPS Module 04
ON/OF F
ENT ER
R ES ET
ON/OF F
UPS Module 03
UPS Module 02
UPS Module 01
Figure 2.1 PowerWAVE 9500DPA System hardware
1 Module
2 Module
3 Module
100
200
539
648
1580 x 1975 x 940
4500
9000
13500
15395
30717
46076
5710
11420
17130
19488
38976
58465
660
1320
75/67dBA (with 5 modules fitted)
1200
2400
Front 1500, Side 100, Rear 200, Top 400
Active sub-module = 55 kg, Passive sub-module = 54 kg
Active & Passive modules 710 x 178 x 750
TS_622_02 PowerWAVE 9500DPA User Manual 26/2/19
ON/ OF F
ENT E R
RES E T
ON/ OF F
Load protected
dd.mm.yy
hh:m m:ss
P:01
load
r ectifier
in ver ter
ON/ OF F
ENT E R
RES E T
ON/ OF F
UPS Cabinet
ON/ OF F
ENT E R
RES E T
ON/ OF F
ON/ OF F
ENT E R
RES E T
ON/ OF F
ON/ OF F
ENT E R
RES E T
ON/ OF F
4 Module
5 Module
300
400
500
757
866
975
430
18000
22500
61434
76793
22840
28550
77953
97441
1980
2640
3300
3600
4800
6000

Advertisement

Table of Contents
loading

Table of Contents