14 FAILURES

In most cases, the controller detects a malfunction of the heating
system and indicates this with a failure notification appearing on
the display. When failure notification displays on the display,
record the alert exactly to the service book to facilitate the
maintenance operations.

14.1 Alerts

When the alert is active, the
pump's display.
More information about the alert can be found on the info page.
Always try first to find out for yourself the malfunction with the
help of the trouble shooting table. If you cannot detect the mal-
function, contact a qualified technician.

14.2 Troubleshooting

If failures are not displayed on the screen, follow the instructions
below.
Basic measures:
1.
Check all switches
2.
Inspect the house as well as the heat pump fuses
3.
Check the fault current circuit breaker
Room temperature too low:
15. Heat pump in incorrect operating mode
16. Set the heat pump heating functions into the right
mode.
17. Thermostats of radiators / floor heating are switched
off
18. Turn on the thermostats in so many rooms as possible
19. Adjust the room temperature on the menu Heating
circuit instead of switching off the thermostats
20. The automatic set point is too low:
21. Raise the Comfort set point on the menu Heating cir-
cuit
Increase the heating curve slope set point
o
on the menu Heating circuit
Set the maximum output water set point
o
sufficiently high on the menu Heating cir-
cuit
Program for heating circuit is switched on
Go to menu Time program heating circuit
o
and adjust the time program to wanted level
Air in the heating system
Vent the heating system
o
Valves closed between the accumulator and the heat-
ing circuit
Open the valves
o
External switch for the room temperature drop acti-
vated
Check any external switches
o
Room temperature too high:
Heating circuit setting values are too high
44
symbol appears on the heat
If the room temperature is too high only in
o
cold weather, decrease the heating curve
slope.
If the room temperature is too high on
o
warm weather, decrease comfort set point.
Domestic hot water too cold:
Domestic hot water function is not active
Pres the domestic hot water selection but-
o
ton so that a black bar appears below the
tap.
Domestic hot water consumption is too high
Wait until the water has warmed up. Tem-
o
porarily at beginning of the higher con-
sumption, you can choose the forced charg-
ing of domestic hot water by pressing the
terminal's domestic hot water button for 3
seconds.
Set point too low
Go to menu Domestic hot water and in-
o
crease the set point for domestic hot water
The feed mixing valve adjusted too low
Open the valve
o
The compressor will not start:
No need for heat
Check heat pump's status on the Menu Info
o
Compressor minimum idle time is active
Wait for 20 minutes and check if the com-
o
pressor will start
Heat pump failure
Check Info menu for the reason for the fail-
o
ure and make the adjustments needed ac-
cording to the trouble shooting table.