ABB 600T Series Operating Instruction page 8

Field indicator

Advertisement

COMETER only
ConF
METER
ENTER
ESC
NEXT
ConF
PREV
AUT O
ENTER
ESC
. . . *
LOADING
NEXT
PREV
ConF
ESC
UPDA TE?
ENTER
ConF
ESC
OK
ENTER
ESC
UPDATE ZERO,
FULL-SCALE
AND UNIT
ESC
The other options under ConF METER menu are:
ConF AUTO
By selecting this option, the CoMeter is automatically updated
with the LRV, URV and Unit of the HART transmitter connected.
Before accepting the transmitter configuration by pressing
ENTER at the request "ConF UPDATE?", it is possible to view
the LRV (ZERO), the URV (FULL SC) and the UNIT.
If the output transfer function of the transmitter is not linear,
ProMeter and CoMeter shows the message: ConF NO_LIN
and the user cannot update the configuration.
It is necessary to change the output transfer function of the
transmitter to linear.
See Fig. 7 - "ConF METER" menu, for ConF AUTO procedure.
- 8 -
ConF
NEXT PREV
MANUAL
ENTER
ESC
NEXT
PREV
OUTPUT
ENTER
ESC
ConF
LINEAR
VIEW ?
SQR
ENTER
ENTER
0.000
ZERO
NEXT
PREV
40.000
FULL SC
NEXT
PREV
KP A
NEXT
PREV
NEXT
PREV
CURRENT
ESC
UPDA TE?
Fig. 7 - ConF METER menu
CALIBRATION PROCEDURE . . .
COMETER and PROMETER
NEXT
NEXT
4000
PREV
PREV
ZERO
ENTER
ESC
ESC
04000
04000
04000
00000
00000
ZERO
ENTER
NEXT
ConF
ConF
PREV
PERCENT
ENTER
ESC
ConF
LINEAR
SQR
ENTER
ESC
ConF
SET 4÷20 mA
INDICATION
UPDA TE ?
SET 0÷100% INDICATION
(WITH OR WITHOUT
ConF MANUAL
The selection of MANUAL configuration allows the user
to define manually the CoMeter configuration, i.e. define
the LRV (ZERO), the URV (FULL SC), and the UNIT, as well
as to decide for a LINEAR on SQR output function. LRV
and URV can have a value between -99999 and +99999.
Refer to Fig.7 - ConF METER menu for detail on the pro-
cedure.
For having the CoMeter to display the analog output current
or the output percentage, select respectively:
ConF CURRENT and ConF PERCENT
NEXT PREV
NEXT
20000
PREV
FULL SC
UNITS
ENTER
ESC
20000
20000
KP A
20000
T ORR
20000
ATM
20000
MPA
FULL SC
IN H2O
ENTER
KG / CM2
ENTER
NEXT
PREV
ConF
PASSWD
ENTER
ESC
00000
01000
01200
01230
01234
ENTER
PASSWD
ESC
ENTER
UPDA TE?
SQUARE ROOT)
NEXT
PREV
ENTER
NEXT
PREV
ENTER
ENTER
ENTER
UPDATE NEW
PASSWORD

Hide quick links: