  • Page 3: Table Of Contents

    CATALOG 1 TP SERIES HMI ..............................1 1-1 Features ..........................1 1-1-1 Product features ....................1 1-1-2 Model naming rule ....................1 1-1-3 Product models...................... 2 1-2 General specifications ....................2 1-3 Hardware .......................... 3 1-3-1 Hardware structure ....................3 1-3-2 Port introduction ....................
  • Page 5: Tp Series Hmi

    1 TP series HMI Features Xinje TP series HMI have strong functions. It supports multi-language, any font and size of characters. The basic functions include data display and monitoring, alarm, recipe. It can communicate with most brands of PLC, two ports can communicate individually. The programming software Touchwin has friendly interface and easy to operate.
  • Page 6: Product Models

    1-1-3 Product models TP series HMI can connect to PLC, inverter, meters and other devices. As the interface of machine and user, it can monitor data, control the machine operation. It is fit for small and medium control systems. Model...
  • Page 7: Hardware

    Nameplate Power supply Download port PLC port 1-3-2 Port introduction Xinje TP series HMI have two communication ports: Download port and PLC port, below is the feature and function of TP series, take the ports of TP460-L as an example:...
  • Page 8 Unused terminal (1) Download function When you use download function of TP series, please use Xinje special download cable: Before user download a program, please make sure your PC has installed multiport serial card or USB-RS232 convertor, and connect cable correctly, click “...
  • Page 9 Power on, move away the shorted line; c. Start to download the program with special download cable. BUSY (2) Communication function The download port of TP series not only has the download function, but also has the powerful communication function. TP Series HMI Send data...
  • Page 10 2. Communication interface of PLC The PLC communication port of TP series has below function:  Connect and communication with industrial control equipments: PLC, inverter, meter etc. The pins definition of PLC communication port: Definition Description RS422 send “+” RS232 receive RS232 send RS485 “+”...
  • Page 11: Dimension And Installation

    (2) Communicate with inverter TP can communicate with various brands of frequency inverters. For the brands which are not in the list, user can select Modbus protocol or user-defined protocol. TP series Mitsubishi FR series inverter Inovance MD series inverter...
  • Page 12: Installation And Using Environment

    5. Connect TP and PLC with communication cable Notice: The communication cable can be offered by the supplier or made by user according to the connection diagram, input +24V DC power to start working. Environment: Please use TP series touch screen indoor.
  • Page 13 Inflammable gas, steam, dust, fast vary temperature, high humidity (it may cause moisture inside TP). Power supply requirements: TP series touch screen use DC +24V power supply only. The permitted voltage range is 20V~26V. The connection is as below: +24V 0 V...
  • Page 14: Th Series Hmi

    TH series HMI 2-1 Features Xinje new touch screen TH series are based on TP series products. It not only has the language, characters editing, data display, monitor and alarm functions but also has 65536 true color LCD which can bring you brand-new vision enjoyment. It has the advantage of large capability for data duplication and friendly user interface.
  • Page 15: Model Naming Rule

     Communication  Two ports communication independently, can connect two different devices at the same time  Drive the panel printer directly, economical and flexible  Support free format communication, user edits the driver program 2-1-2 Model naming rule □□○○○—□□ 1:Series name 2:LCD size 465:4.3”...
  • Page 16: General Specifications

    TH series HMI configuration form PORT1 PORT3 Resolution PORT2 USB-A Download Series Model Screen Download size (pixel) PLC port port port port TH465-MT TH465-UT 232/485/42 TH465-MT 4.3″ 480*272 TH465 TH465-UT 232/485/42 TH765-MT 128M 7.0″ 800*480 232/485 TH765-M TH765-UT TH765-NT TH765-NU USB-B 232/485/42 TH765-NT...
  • Page 17 panel More than 50000 hours, 24 hours running when surrounding Use life temperature is 25 ℃ Character Chinese, English, Korean, Japanese… Character Any size and font size Screen 128MB Memory Electrical specifications Item TH465 TH765 TH865 THA62 THA65 Input DC24V(Range:DC22V-DC26V) voltage Consumptio 130mA...
  • Page 18: Hardware

    COM1 RS232/RS485/RS422 COM2 RS232 RS232/RS485 Expand port RS485 USB 1 USB-A (accord with USB2.0) USB 2 USB-B (accord with USB2.0) 2-3 Hardware 2-3-1 Hardware structure Below is the back side of TH series HMI: USB-A Nameplate USB-B Power supply DIP switch COM 1 COM 2 2-3-2 Port introduction...
  • Page 19 1. DIP switch TH series has 4-bit DIP switch at the back side; they can set the function of COM1 port. Switch DIP1 DIP2 DIP3 DIP4 Function Interior check mode ( not recommended to users) Force-download mode System menu : Adjust clock and touch panel, State Import program of U disk Undefined...
  • Page 20 The pins definition of COM2: Name Description RS422 send + RS232 receive RS232 send RS485 + signal Signal ground RS422 send - RS485 - RDD- RS422 receive - RDD+ RS422 receive + The COM1 pins definition of TH765-NT3/NU3 series: Name Description RS485 + signal RS232 receive...
  • Page 21 (1) Communication with PLC TH series HMI can communicate with most of popular PLCs: SIEMENS TH series Panasonic PLC COM port Other PLCs… Please select correct PLC port (COM2) device and communication parameters: COM2 device selection COM2 communication parameter setting Select the correct download port (COM1) device and communication parameters: COM1 device selection COM1 communication parameter setting...
  • Page 22 (2) Communication with inverter TH can communicate with various brands of frequency inverters. For the brands which are not in the list, user can select Modbus protocol or user-defined protocol. Mitsubishi FR series inverter Inovance MD series inverter Bosch Rexroth Indracontrol COM port (3) Communicate with meters About the communication between TH and meters, users can select user-defined protocol...
  • Page 23 USB-B port definition (1) Please use shielded USB cables. TH back side USB cable (2) Please install USB driver before using. Download the driver from www.xinje.com. (3) Connect TH with PC, open Touchwin software, click “ ” to download the program.
  • Page 24: Dimensions And Installation

    1 2 3 4 1 2 3 4 +0.5 144.0 41.8 152.0 TH765-M/TH765-N (Unit: mm) 43.9 204.0 +0.5 192.0 190.0 THINGET MODE: TW760T S/ N: N20081028028 Xinje Electronic Co.,Ltd 24V 0V FG COM1 COM2 1 2 3 4 1 2 3 4...
  • Page 25 TH865 (Unit: mm) 45.5 224.4 38.0 +0.5 211.4 209.4 1 2 3 4 24V 0V FG 1 2 3 4 Download THA62 (Unit: mm) 272.2 51.2 +1.0 260.2 258.2 24V 0V FG 1 2 3 4 Download...
  • Page 26: Installation And Using Environment

    THA65 (Unit: mm) 48.0 300.0 43.1 +1.0 302.0 311.0 2-4-2 Installation and using environment Install requirements: TH has four ferric mounting racks when out of factory, there are two square holes on the up, down side of TH, use mounting rack to fix the TH with control cabinet. In order to avoid TH temperature too high after long time working, please keep 10cm space on the up/down and 5cm on the left/right side of the TH when installing.
  • Page 27 Environment: Please use TH series touch screen indoor. Do not use TH in below environment: Inflammable gas, steam, dust, fast vary temperature, high humidity (it may cause moisture inside TH). Power supply requirements: TH series touch screen use DC +24V power supply only. The permitted voltage range is 20V~28V.
  • Page 28: Tg Series Hmi

    TG series HMI 3-1 Features Xinje TG series HMI have high quality display: 16 million true color TFT-LCD, support BMP and JPG format, have rich 3D photo gallery, has the flexible components choice space, user-defined animation, convenient mode setting switch, precise touch calibration...
  • Page 29: Module Naming Rule

    3-1-2 Module naming rule □□○○○—□□ 1:Series name 2:Display size 765: 7.0’’ 865: 8.0” A62: 10.1” C65: 15.6’’ 3:Interface type E: USB-B, USB-A, Ethernet port U: USB-B, USB-A M: USB-B 4:Display type T: TFT-LCD Special models TG765-XT: compact type of TG765-MT, it has USB-B port, one RS232 port, without clock.
  • Page 30: General Specifications

    3-2 General specifications HMI specifications Item TG765 TG865 TGA62 TGC65 7.0″ 8.0″ 10.1″ 15.6’’ Size 16 million colors Type 800*480 800*600 800*480 1366*768 Resolution Brightness Adjustable (through register PFW100) Non-adjustable Screen Touch panel 4-wire resistance mode More than 50000 hours, temperature 25℃, running for 24 hours Using life Chinese, English, Japanese, Korean, German, French, Language...
  • Page 31: Hardware

    Anti-jamm Voltage noise:1500Vp-p,pulse 1us,1 minute Surroundi No corrosive gas ng air Protection constructi IP65 Cooling Natural air cooling method Exterior 200.4*146.9* 224.4*170.8* 272.2*191.7* 410.0*270.0* Construct dimension 43.4 45.5 51.2 65.0 (mm) Mounting 192.0*138.5 211.4*157.8 260.2*179.7 399.0*259.0 dimension (mm) RS232/RS485/RS422 (TG765-XT, TG765-XT-C only support PLC port RS232) Download...
  • Page 32: Ports Introduction

    Nameplate USB-A USB-B RJ45 Power supply 1 2 3 4 24V 0V FG 1 2 3 4 Download Download port PLC port DIP switch 3-3-2 Ports introduction TG series HMI port: Outline Name Function DIP switch Force-download, touch area adjustment 1 2 3 4 1 2 3 4 Download port...
  • Page 33 1. DIP switch TG series has 4-bit DIP switch at the back side; they can set the function of COM1 port. Switch DIP1 DIP2 DIP3 DIP4 Function Interior check mode ( not recommended to users) Force-download mode State System menu: Adjust clock and touch panel, Import program of USB flash drive Undefined If the screen cannot show normally after downloading the program, please use...
  • Page 34 RS422 send - RS485 - signal RDD- RS422 receive - RDD+ RS422 receive + TG765-XT, TG765-XT-C PLC port: Name Description Unused terminal RS232 receive RS232 send Unused terminal Signal ground Unused terminal Unused terminal Unused terminal Unused terminal 3. USB-A port USB-A (accord with USB2.0) of TG series HMI has below function: ...
  • Page 35: Dimensions And Installation

    (1) Please use shielded USB cables. (2) Please install USB driver before using. Download the driver from www.xinje.com. (3) Connect TH with PC, open Touchwin software, click “ ” to download the program. 5. RJ45 port The pins definition of RJ45 port...
  • Page 36 43.4 200.4 192.0 190.0 THINGET MODE: TG760T-MT S/ N: N20121028028 Xinje Electronic Co.,Ltd 24V 0V FG COM1 COM2 1 2 3 4 1 2 3 4 TG765-XT, TG765-XT-C (Unit: mm) 43.4 200.4 1 9 2 . 0 190.0 TouchWin MODE: TG760T-XT S/ N: N20121028028 Xinje Electric Co.,Ltd...
  • Page 37 TG865-MT/UT/ET (Unit: mm) 45.5 224.4 38.0 211.4 209.4 1 2 3 4 24V 0V FG 1 2 3 4 Download TGA62-MT/ET (Unit: mm) 272.2 51.2 260.2 258.2 24V 0V FG 1 2 3 4 Download...
  • Page 38: Installation And Using Environment

    TGC65-MT/UT/ET (Unit: mm) 65.0 399.0 56.5 410.0 395.0 24V 0V FG 1 2 3 4 Download 3-4-2 Installation and using environment Install requirements: TG has four ferric mounting racks when out of factory, there are two square holes on the up, down side of TG, use mounting rack to fix the TG with control cabinet.
  • Page 39 4. Insert the install rack into the fix hole of TH then tighten the screw; 5. Connect TH and PLC with communication cable. Notice: The communication cable can be offered by the supplier or made by user according to the connection diagram, input +24V DC power to start working Environment: Please use TG series touch screen indoor.