LED Maintained Emergency
Recessed Fitting
Installation Instructions p.1
For models: LFACLED502F
This installation must be carried out by an electrician.
Please read these instructions carefully before installation.
Leave a copy for the user/maintenance engineer for future reference.
Specification
220-240V
2.5W Wattage
6.5W Power consumption
50pcs of Ø5 LED
297 Lumen output (201lm in emergency mode)
6000-7000K Colour temperature
> 3 Hours emergency duration
24 Hours charging time
Installation
1.
Remove the diffuser from the body by removing the two
screws.
2.
Release gear tray by removing the two retaining screws.
3.
Cut out hole for fitting, 120 x 340mm, in the ceiling tile.
4.
ISOLATE THE A.C. SUPPLY and connect unit. An
unswitched 240V A.C. supply must be connected to the Live
(L). Earth and Neutral (N) terminals on the PCB block. On
Maintained circuits continuous illumination can be achieved
by connecting a link between L and Lsw either locally or
through a remote switch.
5.
Place the fitting into the hole and screw the arm screws so
that the arms are fully down.
6.
Allow the fitting to rest on the arms.
7.
Plug battery lead into connector on the PCB.
8.
Locate the bezel under the fitting and secure using the 2
long screws supplied.
9.
Re-secure the gear tray into the base of the unit making
sure that the mains cable is not trapped by the PCB etc.
10.
Operational check - restore the A.C. supply for 30 minutes
and then remove. The LEDs should illuminate for at least
10 seconds.
11.
Restore the A.C. supply and check that the indicator LED
is 'on.'
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
ENSURE FITTING IS CHARGED FOR A MINIMUM OF 24
HOURS PRIOR TO TESTING.
Quick Guide
1.
2.
3.
T: 0800 195 0006
F: 0870 043 3946
E: sales@redarrowtrading.com
www.redarrowtrading.com

Advertisement

loading

Summary of Contents for Red Arrow Trading LFACLED502F

  • Page 1 LED Maintained Emergency Recessed Fitting Installation Instructions p.1 For models: LFACLED502F This installation must be carried out by an electrician. Please read these instructions carefully before installation. Leave a copy for the user/maintenance engineer for future reference. Specification ENSURE FITTING IS CHARGED FOR A MINIMUM OF 24 HOURS PRIOR TO TESTING.
  • Page 2 LED Maintained Emergency Recessed Fitting Installation Instructions p.2 For models: LFACLED502F Operation Non-Maintained Lamp normally off and battery on automatic charge (LED ‘on’) when A.C. supply is healthy. Solid state circuitry automatically switches lamp on when A.C. supply is interrupted.
  • Page 3 LED Maintained Emergency Recessed Fitting Installation Instructions p.3 For models: LFACLED502F LEDs Not Fully Illuminated If the LEDs are not illuminated check connections & if correct either the battery pack or (less likely) the printed circuit board needs replacing. RECOMMENDED ROUTINE TEST PROCEDURE The following test is designed to ensure the continued protection of your premises and occupants.