Download Print this page

Red Arrow Trading LFACLED502F Installation Instructions page 3

Led maintained emergency recessed fitting

Advertisement

LED Maintained Emergency
Recessed Fitting
Installation Instructions p.3
For models: LFACLED502F
LEDs Not Fully Illuminated
If the LEDs are not illuminated check connections & if correct either the battery pack or (less likely) the printed circuit
board needs replacing.
RECOMMENDED ROUTINE TEST PROCEDURE
The following test is designed to ensure the continued protection of your premises and occupants. Because of the
possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should whenever
possible, be undertaken at times of least risk, e.g. during daylight hours.
ONCE A DAY
Visual inspection of battery charge led.
ONCE A MONTH
Each unit should be energised from it's battery for adequate time to ensure, by simulation of a failure of the normal
lighting supply, the emergency mode is functioning correctly.
ONCE A YEAR
All units should be placed into emergency mode and checked that the duration provided by the battery meets the specified
time period. Clean the internal and external surface of the diffuser.
Month
Test
signed
1
Functional
2
Functional
3
Functional
4
Functional
5
Functional
6
1 hour
7
Functional
8
Functional
9
Functional
10
Functional
11
Functional
12
1 hour
3 hour
Guarantee
This product is guaranteed for a period of 1 year from the date of purchase. The guarantee is invalid in the case of improper use, tampering, removal of the Q.C. date label, installation in
an improper working environment or installation not according to the current edition of the I.E.E. Wiring Regulations (BS7671). The guarantee is also invalidated if the luminaire has
been Mega tested. Should this product fail during the guarantee period it will be replaced free of charge, subject to correct installation and return of the faulty unit. We do not accept
responsibility for any installation costs associated with the replacement of this product. We reserve the right to alter specifications without prior notice.
Red Arrow Trading
Elsworth House, Herries Road South
Sheffield, S6 1QS
Year 1
Year 2
date
signed
date
Year 3
signed
date
signed
F
Product is suitable for
mounting on flammable
material
T: 0800 195 0006
F: 0870 043 3946
E: sales@redarrowtrading.com
Year 4
Year 5
date
signed
date
Product complies with
all relevant European
standards
www.redarrowtrading.com