SERVICE FUNCTIONS

MSY-TP35VF MSY-TP50VF
8-1. TIMER SHORT MODE
For service, the following set time can be shortened by bridging the timer short mode point on the electronic control P.C.
board. (Refer to 10-7.)
Set time : 3-minute → 3-second (It takes 3 minutes for the compressor to start operation. However, the starting time is
NOTE: While the relay 52C is ON, the compressor starting time cannot be shortened.
8-2. AUTO RESTART FUNCTION
When the indoor unit is controlled with the remote controller, the operation mode, the set temperature, and the fan speed
are memorized by the indoor electronic control P.C. board. "AUTO RESTART FUNCTION" automatically starts operation in
the same mode just before the shutoff of the main power.
Operation
If the main power has been cut, the operation settings remain.
After the power is restored, the unit restarts automatically according to the memory.
(However, it takes at least 3 minutes for the compressor to start running.)
How to disable "AUTO RESTART FUNCTION"
Turn off the main power for the unit.
Cut the Jumper wire to JR77 on the indoor electronic control P.C. board. (Refer to 10-7.)
NOTE:
The operation settings are memorized when 10 seconds have passed after the indoor unit was operated with the remote
controller.
If main power is turned OFF or a power failure occurs while AUTO START/STOP timer is active, the timer setting is can-
celled.
If the unit has been turned OFF with the remote controller before power failure, the auto restart function does not work
as the power button of the remote controller is off.
To prevent the breaker from tripping OFF due to the rush of starting current, systematize other home appliance not to
turn ON at the same time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter measures are required to prevent the main voltage-drop or the rush of the starting current
by adding to the system that allows the units to start one by one.
OBH816
shortened by bridging the timer short mode point.)