Model 962PB-2006 Six Differential Voltage Inputs USER’S MANUAL ACROMAG INCORPORATED Tel: (248) 624-1541 30765 South Wixom Road Fax: (248) 624-9234 Wixom, MI 48393-2417 U.S.A. Copyright 2002, Acromag, Inc., Printed in the USA. 8500692D Data and specifications are subject to change without notice.
Symbols on equipment: loss or human life is involved. It is important that you perform satisfactory overall system design and it is agreed between you and Acromag, that this is your responsibility. GETTING STARTED Means Refer to User’s Manual (this manual) for additional MOUNTING AND DIMENSIONS………………………...
INPUTS 4, 5 barriers. TRANSFORMER OPTICAL The input circuit, network, and power circuit are isolated from each other for safety and noise immunity. INPUTS 0, 1 INPUTS 2, 3 25 26 INPUTS 0,1 INPUTS 2,3 _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
(do not twist the PRY WITH SCREWDRIVER INSERTED IN SLOT HERE (DO NOT TWIST TO AVOID screwdriver to avoid damaging plastic). DAMAGING PLASTIC TAB) PUSH SCREWDRIVER AS SHOWN TO TILT AND LIFT MODULE OFF RAIL _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
For baud rates not shown, the lower length of the closest range end points apply (i.e. 100M at 3Mbps). Note that Acromag modules Bus Segment Length Limit Per Baud Rate For Type A Bus Cable...
NOTE 1: THIS GROUND CONNECTION IS RECOM M ENDED FOR BEST RESULTS. IF SENSORS ARE INHERENTLY CONNECTED TO GROUND, USE CAUTION AND AVOID M AKING ADDITIONAL GROUND CONNECTIONS WHICH COULD GENERATE GROUND LOOPS AND M EASUREM ENT ERROR. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
Page 7
IN0- IN1+ IN1+ IN1- IN1- DIFFERENTIAL VOLTAGE MONITORING NOTE: 962PB INPUTS ARE NOT ISOLATED CHANNEL-TO- CHANNEL, EXCEPT FOR COMMON MODE VOLTAGES LESS THAN +/-5V. AS SUCH, LIMIT BRIDGE EXCITATION TO 5V OR LESS. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
The metal shroud of the DB9 ProfiBus connector on (IF NECESSARY--SEE NOTE) Use only approved cables Acromag modules is common to pin 1 of the DB9 with braided shields of connector (SHIELD). This is also common to the density greater than 80%.
Detect signal reflections along the network, useful for locating bus line interruptions and discontinuities. Acromag strongly suggests the use of these tools for building and maintaining ProfiBus networks. Note that Profichip also offers a Profibus connector (PA003100) that includes 4 network diagnostic LED’s that may be helpful in trouble-shooting your network (see table below).
LED ON? exchange the module with a Is address correct? Check slave address setting. known good unit. Acromag’s Is the termination Switch Termination on only at Application Engineers can switch of the the ends of the network.
4. Write FFH into the low-order byte of the channel’s output word several times (to ensure transmission). In Configuration Mode, the module will automatically calibrate the channel’s zero value when FFH is detected. Then write 00H into the low-order byte to complete zero calibration. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
Page 12
“Input Mode” configuration, and the slave will then be taken off-line by the master and reconfigured. If reconfiguration is successful, the slave module will pass to the data exchange state with a normal I/O configuration. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
Hardened For Harsh Environments - For protection from RFI, EMI, ESD, EFT, & surges. Has low radiated emissions per CE requirements. Wide Ambient Operation – Reliable over a wide temperature range. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
A/D converter. An optional external sensor is required to monitor AC current signals (Acromag Model 5020-350). This sensor generates a DC milliampere signal of 0 to 11.17mA for the module (see Table 1 below for scaling to AC current).
Case Material: Self-extinguishing NYLON type 6.6 polyamide thermoplastic UL94 V-2, color beige; general purpose NEMA Type 1 enclosure. Printed Circuit Boards: Military grade FR-4 epoxy glass. Shipping Weight: 1 pound (0.45 Kg) packed. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
900MHz keyed carrier, per EN61000-4-3 and ENV50204. with higher standards in some Electrical Fast Transient Immunity (EFT): 2KV to power, and 1KV to cases. signal I/O per EN61000-4-4. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
244 bytes of data/node/message, plus 11 bytes of overhead (frame). ProfiBus Character: 11 bits (1 start bit + 8 data bits + 1 even parity bit + 1 stop bit). Applies to all bytes, including frame bytes. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
MSB & LSB of the 8 bit slave address. See Address above. I/O values of Acromag 9xxPB modules are represented by the following Data Types simple data types for temperature, percentage, and discrete on/off. Note that when transferring words, data bytes are transmitted using “Big Endian”...
Writing 55H to this register will cause the module to restore its original factory calibration. Note that 55H is not stored, but acts as a trigger, as this byte always reads as 00H. Factory Use Only – Do Not Modify. _______________________________________________________________________________________ Acromag, Inc. Tel:248-624-1541 Fax:248-624-9234 Email:sales@acromag.com http://www.acromag.com...
Page 21
BusWorks® 961/962PB Module User’s Manual ProfiBus Differential I/V Input ___________________________________________________________________ Revision History The following table shows the revision history for this document: Release Date Version EGR/DOC Description of Revision 03 APR 03 BC/KLK Initial release. 28 OCT 03 BC/KLK UL updates per ECN 03J022. 02 NOV 04 CAP/KLK Added latest UL information to manuals and labels per...