FX Mechanical Leak Detectors
Quick Troubleshooting Guide
• Veeder-Root makes no representation or warranty about the information in this publication. A qualified professional is
required for service of the components addressed in this publication.
• The information in this publication cannot be used as a substitution for the knowledge and experience of a qualified
professional.
• The information contained in this publication is merely for the consideration of a qualified professional, which should make
their own determination of how to address any issues based on the situation.
• Veeder-Root shall not be liable for errors contained herein or for any type of damages in connection with the furnishing,
performance, or use of this publication.
• Veeder-Root reserves the right to change system options or features, or the information contained in this publication, at any
time without notice.
• This publication contains proprietary information which is protected by copyright. All rights reserved. No part of this
publication may be photocopied, reproduced, or translated to another language without the prior written consent of Veeder-
Root.
• Contact TLS Systems Technical Support for additional troubleshooting information at 800-323-1799.
Contractor Certification Requirements
Veeder-Root requires the following minimum training certifications for contractors who will troubleshoot the equipment
discussed in this manual:
Installer Certification: Contractors holding valid Installer Certification are approved to perform wiring and conduit routing,
equipment mounting, probe and sensor installation, tank and line preparation, and line leak detector installation.
Safety Warnings
FAILURE TO COMPLY WITH THE FOLLOWING WARNINGS AND SAFETY PRECAUTIONS COULD RESULT IN
SERIOUS INJURY OR DEATH, AND COULD CAUSE DAMAGE TO PROPERTY AND THE ENVIRONMENT.
EXPLOSIVE: Fuels and their vapors are extremely explosive if ignited.
FLAMMABLE: Fuels and their vapors are extremely flammable.
ELECTRICITY: High voltage exists in, and is supplied to, the device. A potential shock hazard exists.
TURN POWER OFF: Live power to a device creates a potential shock hazard. Turn Off power to the device and associated
accessories when servicing the unit.
WARNING: Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
READ ALL RELATED MANUALS: Knowledge of all related procedures before you begin work is important. Read and
understand all manuals thoroughly. If you do not understand a procedure, ask someone who does.
This system operates near highly combustible fuel storage tanks.
To ensure proper installation, operation, and continued safe use of this product:
1. Read and follow all instructions in this manual, including all safety warnings.
2. Have equipment installed by a contractor trained in its proper installation and in compliance with all applicable codes
including: National Electrical Codes 70 and 30A; federal, state, and local codes; and other applicable safety codes.
3. Before installing pipe threads apply an adequate amount of fresh, UL classified for petroleum, non-setting thread sealant.
For E85AG applications, Loctite 564 is recommended for all field serviceable pipe threads.
4. When servicing unit, use non-sparking tools and use caution when removing or installing equipment to avoid generating a
spark.
5. Substitution of components may impair intrinsic safety.
6. Do not modify or use service parts other than those provided by Veeder-Root.
1
Manual No: 577014-340
Revision: A

Advertisement

loading

Summary of Contents for Veeder-Root FX

  • Page 1 • Veeder-Root shall not be liable for errors contained herein or for any type of damages in connection with the furnishing, performance, or use of this publication.
  • Page 2 5. Confirm actual induced leak is at least 3 GPH equivalent. Calculate as necessary. 6. Review FX leak detector tests per C051-272. Compare actual test procedure to approved Veeder-Root test procedure. 7. Replace unit if minimum leak detected is greater than 3 GPH or if it exceeds your company’s specifications.
  • Page 3 11. Device should open (full pump pressure) in approx. 3-5 seconds. If it still doesn’t open replace the FX with a new unit. 12. Contact Red Jacket tech support at 800-323-1799 if new unit does not resolve concerns.