Desert Aire Aura QS Installation And Operation Manual page 26

Indoor air quality
Table of Contents

Advertisement

Note: When sizing supply lines, consider possibilities of future expansion and
26
Desert Aire - QS/QV Manual
Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Natural Gas - 0.6 (Natural Gas - 1000BTU/Cubic Ft.)
Specific Gravity for Propane Gas - 1.6 (Propane Gas - 2550BTU/Cubic Ft.)
Length
of
1/2"
Pipe
Natural
Propane
20'
92
30'
73
40'
63
50'
56
60'
50
70'
46
80'
43
90'
40
100'
38
125'
34
150'
31
175'
28
200'
26
Length
1-1/4"
of
Pipe
Natural
Propane
20'
730
30'
590
40'
500
50'
440
60'
400
70'
370
80'
350
90'
320
100'
305
125'
275
150'
250
175'
225
200'
210
Refer to National Fuel Gas Code for additional information on line sizing.
Figure 9 - Gas Pipe Capacity in Cubic Feet per Hour
Capacity of Piping
Diameter of Piping
3/4"
Natural
Propane
56
116
190
45
152
38
130
34
115
31
105
28
96
26
90
24
84
23
79
21
72
19
64
17
59
16
55
Diameter of Piping
1-1/2"
Propane
Natural
445
1100
671
360
543
890
305
760
464
268
409
670
244
610
372
226
342
560
214
323
530
195
299
490
186
281
460
168
410
250
153
232
380
137
350
214
128
195
320
increased requirements.
1"
Propane
Natural
214
350
93
174
285
79
149
245
70
131
215
64
119
195
59
110
180
55
104
170
51
98
160
48
92
150
44
79
130
39
73
120
36
67
110
34
61
100
2"
Propane
Natural
1281
2100
1007
1650
885
1450
775
1270
674
1105
641
1050
604
990
567
930
531
870
476
780
433
710
397
650
372
610

Hide quick links: