TotalAire™ and VerticalAire™ Products Flow Rate
The flow rate and antifreeze concentration (if used) will depend on the application. Please refer to Figure 6
and 7 for the required flow rate and temperature limits for the given application and unit type as well as the
glycol concentration requirements. If the application exceeds these conditions, please contact Desert Aire
Service at 262-946-7400 for further review.
18
Desert Aire - QS/QV Manual
Glycol Percent
0
5
10
15
20
25
30
35
40
45
50
Figure 5 - Aura™ Q-Pump Minimum Water Temperature
Min. Fluid Temp. (°F)
40
37
34
31
27
25
25
25
25
25
25