AS-Interface Slaves
I/O modules for operation in IP20 control cabinet
SlimLine
Technical specifications (continued)
Total current input in mA
Inputs
• Sensor supply via AS-Interface
• Voltage range in V
• Current carrying capacity
for sensor supply in mA
• Connection of sensors
• Switching level High in V
• Input current Low/High in mA
Outputs
• Type of output
• Current carrying capacity
per output in A DC 12 / DC 13 typ.
• Maximum summation current
per module in A
• Short-circuit protection
• Inductive interference protection
(free-wheeling diode)
6
• Polarity reversal protection
• External 24 V DC supply voltage
• I
th
• AC-15
• DC 13 24 V
• DC 13 110 V
• DC 13 230 V
• Watchdog
I/O configuration
ID/ID2 code
Assignment of data bits
• Data bit D0
• Data bit D1
• Data bit D2
• Data bit D3
Connection
Conductor cross-sections in mm
Note 1
Note 2
6/84
Siemens IK PI · 2004
4 inputs/4 outputs
Spring-loaded connection
Standard slave
2- and 3-wire
PNP transistor (1 A)
3RK1 402-3CG01-0AA2
40
Short-circuit and overload withstand capability
20 to 30
200
2- and 3-wire system
³
10
³
1.5 /
5
Electronics
1
4
Built-in
Built-in
Built-in
Sensor supply:
Terminal 13 = U_s+
Terminal 19 = U_s–
Actuator supply:
Terminal 14 = L+
Terminals 20 to 24 = M
--
--
--
--
--
Built-in
7
0/F
IN1/OUT1
IN2/OUT2
IN3/OUT3
IN4/OUT4
Spring-loaded terminal connection
´
2
Solid: 2
(0.25–1.5)
Finely stranded with end sleeve: 2
Finely stranded without end sleeve: 2
AWG conductor connections solid or stranded:
´
AWG 2
(24–16)
Disassembly tool for spring-loaded terminal
connection: See "Accessories"
The module has four floating inputs and four
floating switching outputs. For the input and output
circuits, an external additional supply of 20 to 30 V
according to VDE 0106 (PELV) Safety Class III is
required.
4 inputs/4 outputs
Spring-loaded connection
Standard slave
2- and 3-wire
Relay
3RK1 402-3CG00-0AA2
270
Short-circuit and overload withstand capability
20 to 30
200
2- and 3-wire system
³
10
³
1.5 /
5
Relay
--
--
External back-up fuse 6 A gL/gG
Not applicable
Built-in
Not applicable
5
3
1
0.2
0.1
Built-in
7
0/F
IN1/OUT1
IN2/OUT2
IN3/OUT3
IN4/OUT4
Spring-loaded terminal connection
´
Solid: 2
(0.25–1.5)
´
(0.25–1)
Finely stranded with end sleeve: 2
´
(0.25–1.5)
Finely stranded without end sleeve: 2
AWG conductor connections solid or stranded:
´
AWG 2
(24–16)
Disassembly tool for spring-loaded terminal
connection: See "Accessories"
--
´
(0.25–1)
´
(0.25–1.5)