COVER
Fig. 42 — Pivot and Support Top Cover
3.
Remove all surface loaded fibers and dirt with a vacuum
cleaner. If a vacuum cleaner is not available, a soft non-
metallic bristle brush may be used. In either case, the tool
should be applied in the direction of the fins. Coil sur-
faces can be easily damaged (fin edges can be easily bent
over and damage to the coating of a protected coil) if the
tool is applied across the fins.
NOTE: Use of a water stream, such as a garden hose, against
surface loaded coil will drive the fibers and dirt into the coil,
making cleaning efforts more difficult. Surface loaded fibers
must be completely removed prior to using low velocity clean
water rinse.
4.
Using a low velocity garden hose thoroughly wet finned
surfaces with clean water. Be careful not to bend the fins.
5.
Mix Totaline environmentally sound coil cleaner in a 2
gallon garden sprayer according to the instructions
included with the cleaner. The optimum solution tempera-
ture is 100°F (38°C).
NOTE: Do NOT USE water in excess of 130°F (54°C), as the
enzymatic activity will be destroyed.
6.
Thoroughly apply Totaline environmentally sound coil
cleaner solution to all coil surfaces including the finned
area, tube sheets and coil headers.
7.
Hold garden sprayer nozzle close to finned areas and
RIGID
apply cleaner with a vertical, up-and-down motion.
SUPPORT
Avoid spraying in horizontal pattern to minimize poten-
tial for fin damage.
8.
Ensure cleaner thoroughly penetrates deep into finned
areas.
9.
Interior and exterior finned areas must be thoroughly
cleaned.
10. Finned surfaces should remain wet with cleaning solu-
tion for 10 minutes.
11. Ensure surfaces are not allowed to dry before rinsing.
Reapply cleaner as needed to ensure 10-minute satura-
tion is achieved.
12. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray nozzle.
13. Replace top cover and rear corner posts.

Fastener Torque Values

ITEM
Compressor mounting bolts
Condenser fan motor mounting bolts
Condenser fan hub setscrew
High-flow service port
Schrader-type service check valve
Compressor oil sight-glass thread
1
/
Compressor to Compressor rail torque
2
Compressor rail to base pan torque
39
Table 21 — Torque Values
TORQUE VALUE
65-75 in.-lbs
(734-847 N-cm)
20 ± 2 in.-lbs
(226 ± 23 N-cm)
84 ± 2 in.-lbs
(949 ± 136 N-cm)
96 ± 10 in.-lbs
(1085 ± 23 N-cm)
2-3 in.-lbs
(23-34 N-cm)
330 ± 31 in.-lbs
(23-34 N-cm)
120-168 in.-lbs
(1356-1898 N-cm)
70 ± 5 in.-lbs
(791 ± 57 N-cm)