6.2
6.3
6.4
6.5
HONEYWELL
Test Lamp (Part No. FS-846-B)
This portable, hand-held test lamp is battery-powered for remote
activation of the FS System 10 Flame Detectors. This device
allows the entire Fire Protection System to be tested during start-up
or routine maintenance. This test lamp simulates the radiant
energy emitted by an actual fire in order to test the Detectors
without the need for an open flame. Eight "D" sized replaceable
flashlight batteries are required to power the Test Lamp.
Note
: Refer to the SYSTEM TEST WARNING of Section 3.6.
Disposable Protective Covers for Detectors
(Part No. DPC-12)
Honeywell Analytics' Flame Detectors, with their unique wide
spectral bands, can "see through" factory supplied Disposable
Protective Covers with no reduction in Detector performance (for
end-users with a planned maintenance schedule). Should debris
collect, these specifically designed protective covers may be easily
replaced. The task of cleaning the Detector viewing windows for
proper operation is eliminated
requirements. A regularly scheduled maintenance plan can
virtually eliminate the need to interrupt a production process in
order to clean a Detector's dirty viewing window. Each package
contains twelve (12) Protective Covers.

Extension Pole for Disposable Covers (Part No. EXPL-1)

This extension is used to install or remove the FS System 10
Disposable Protective Covers in hard-to-reach areas. The pole
extends in three sections to a length of 11.0 feet.

Air Shield for Dirty Applications (Part No. DASA1-P)

The Detector Air Shield mounts to the Flame Detector housing for
installation in areas with high levels of airborne contaminants. The
Air line fitting accepts ¼" O.D. nylon tubing for an instrument grade
air supply of 5 to 15 psi @ 6 cubic ft. per minute.