3.2
To Disable a Fault Alarm
Turn the variable resistor (control knob) fully clockwise and then fully anticlockwise
within 5 seconds.
3.3
To Manually Force a Defrost
While pushing in the light switch knob, turn the variable resistor (control knob) fully
clockwise and then fully anticlockwise within 10 seconds.
The resistance of the PC sensor is outside the normal range (>
45K Ohms).
Check sensor resistance.
Check the sensor connection at the control module.
Replace the sensor.
The resistance of the PC sensor is outside the normal range (<
660 Ohms).
Check sensor resistance.
Check the sensor connection at the control module.
Replace the sensor.
The compressor has failed to start after 5 attempts.
Check the integrity of the compressor.
Replace the control module.
The control (variable resistor) has an open circuit fault.
Check the continuity of the circuit between the variable resistor
and control module and the connections at the variable resistor
and control module.
Replace the variable resistor.