Spring Return Operation; Feedback Operation; Direct Checkout; Two-Position Checkout - Honeywell 3 Nm Series Installation Instructions Manual

Spring return direct coupled actuators
Table of Contents

Advertisement

6. Apply control signal for actuator 0% position.
(See Fig. 11 and Table 2.)
a. (0)2-10 Vdc: apply (0)2 Vdc signal to terminal 3.
b. 10-(0)2 Vdc: apply 10 Vdc signal to terminal 3.
c. (0)4-20 mA: apply (0)4 mA signal to terminal 3.
d. 20-(0)4mA: apply 20 mA signal to terminal 3.
e. Floating: apply 24 Vac to appropriate 0°-90° (3) or
90°-0° (4) terminal.
7. Actuator drives to full open or full closed position.

Spring Return Operation

1. Mount actuator for required application (either clock-
wise
or counterclockwise
the damper or valve).
2. Connect power to terminals 1 and 2. (See Fig. 11 and
Table 2.)
NOTE: For two-position models skip to step 5.
3. Set "Mode Select" dial to desired control signal.
(See Fig. 4.)
4. Apply control signal for actuator 50% position.
(See Fig. 11.)
a. Vdc Input Signal: apply 5-6 Vdc signal to terminal 3.
b. mA Input Signal: apply 10-12 mA signal to terminal 3.
c. Floating: apply 24 Vac to appropriate 0°-90° (3) or
90°-0° (4) terminal until device reaches 50%.
5. Allow the actuator to drive to 50% position.
6. Disconnect wire from terminal 1.
7. Actuator spring returns to 0% position.
8. Re-connect wire to terminal 1, actuator drives back
toward 50% position.

Feedback Operation

1. Connect a multi-meter, set for Vdc, to terminals 2 and 5.
2. Apply the same signal as in step 4 of Modulating
Operation.
3. The multi-meter reading increases to match the input
signal as actuator drives towards full open or full closed
position.
4. Apply the same signal as in step 6 of Modulating
Operation.
5. The multi-meter reading decreases to match the input
signal as actuator drives towards 0% position.
3 NM, 5 NM SERIES SPRING RETURN DIRECT COUPLED ACTUATORS

Direct Checkout

1. Mount actuator for required application (either clock-
2. Check damper position and make sure that 24 Vdc/Vac
3. Apply control signal to the appropriate connections to
4. If actuator does not run, verify that the actuator is
5. If actuator is correctly installed and still does not run,
rotation to open

Two-Position Checkout

1. Mount actuator for required application (either clock-
2. Check damper position and make sure that power is
3. Actuator drives to 100% position.
4. Disconnect power from terminals 1 and 2.
5. Actuator spring-returns to 0% position.
If actuator is correctly installed and does not run, replace the
actuator.

Sylk-enabled (S-BUS) Checkout

1. Mount actuator for required application (either clockwise
2. Connect Sylk-enabled (S-BUS) controller to terminals 3
3. Connect power to terminals 1 and 2. (See Fig. 20 and
4. Set "Mode Select" dial to desired address (MS3105
5. Apply S-BUS command via the connected Sylk-enabled
11
wise
or counterclockwise
the damper or valve).
is present at the appropriate connections. (See Fig. 9.)
move the damper to the opposite position. The actuator
should drive the damper or valve.
properly installed for either clockwise
clockwise
rotation.
replace the actuator.
wise
or counterclockwise
the damper or valve).
present at terminals 1 and 2.
or counterclockwise rotation to open the damper).
and 4. (See Fig. 20)
Table 2.)
series). (See Fig. 4.) This step is not necessary for the
MS3103 series.
controller for actuator full open or full closed position.
(See Fig. 20 and Table 2.) The MS3105 series has the
option for local test by setting "Mode Select" dial to 6.
Remember to reset the "Mode Select" dial to the appro-
priate address after the test has been completed.
rotation to open
or counter-
rotation to open
62-0274—07