To set the speed through the Modbus protocol is necessary to set a dedicated register
(Input Type – HOLDING REGISTER 34 see " Modbus communication" paragraph )
In figure 13 is shown how to connect the tachometric output.
The tachometric output is a 0 to 5V PWM waveform at 1KHz with the following duty cycle:
Remember that the Speed
The +10V power supply available of the Driver is intended to be used with a
potentiometer of minimum 2KOhm.
Any different devices connected to it could bring to an undesired functioning of the Driver
or the connected device. The absorbed current must be <5mA.
Don't reverse the input signal or connect the +10V to signal ground.
The Driver could be damaged.
Don't apply signals with voltage higher than 10V
The Driver could be damaged.
th
Rev. 2 – 10
November2015
Fig.13 – Driver – CONTROL BOARD tachometric output connection
90% ∙
10%
= 0 below Speed
Real
0%,
!
!
"#$
min
11