Test Run
Static pressure compensation mode
This function secures the air flow rate of ODU, in case static pressure has been applied like using duct at fan
discharge of ODU.
n Static pressure compensation dip S/W setting method
High static pressure mode : Set DIP S/W
Static pressure compensation mode setting
Static pressure compensation mode is set
Note
How to set the unit to high ESP :
1) Standard ESP (External Static Pressure) : 4mmH
2) High ESP (External Static Pressure) : 8mmH
' The setting of dip S/W is needed. (Refer to above operating method)
92
Outdoor Unit
method
Set the DIP S/W ON
Power Reset
Warning : Please reset Main PCB before starting this function
O (78.4Pa)
2
Static pressure compensation mode cancellation
Static pressure compensation mode is cancelled
DIP Switch Settings
O (39.2Pa)
2
method
DIP switch OFF
Power Reset