Installation Space

Installation Space
Individual Installation
n During the installation of the unit, consider service, inlet, and outlet and acquire the minimum space
as shown in the figures below.
Category
B
A
D
B
A
D
B
4 sides are
A
walls
F
D
B
A
F
D
B
A
Only 2 sides
are walls
B
A
Limitations on
the height of
the wall
(Refer to 4 side
walls)
16
Outdoor Unit
Installation Space
C
Front
E
E
Front
E
C
Front
Front
E
C
Front
Front
No limit to the height of the wall
Front
E
E
Front
• The height of the wall on the front side must be 1500mm(59-1/16 inch) or less.
• The height of the wall on the inlet side must be 500mm(19-11/16 inch) or less.
• There is no limit to the wall on the side.
• If the height of the walls on the front and the inlet are higher than the limit, there
must be additional space on the front and the side.
- Additional Space on the inlet side by 1/2 of h1.
- Additional Space on the front side by 1/2 of h2
- h2 = A(Actual height) - 59-1/16
- h1 = B(Actual height) - 19-11/16
Case 1
(10mm≤Space A, C≤49mm)
A≥10(13/32")
B≥300(11-13/16")
C≥10(13/32")
D≥500(19-11/16")
A≥10(13/32")
B≥300(11-13/16")
C
C≥10(13/32")
D≥500(19-11/16")
E≥20(25/32")
A≥10(13/32")
B≥300(11-13/16")
C≥10(13/32")
D≥500(19-11/16")
E≥20(25/32")
F≥600(23-5/8")
A≥10(13/32")
B≥300(11-13/16")
C≥10(13/32")
D≥300(11-13/16")
E≥20(25/32")
F≥500(19-11/16")
A≥10(13/32")
B≥300(11-13/16")
A≥200(7-7/8")
B≥300(11-13/16")
No limit to the
E≥400(15-3/4")
height of the wall
Case 2
(Space A, C≥49mm)
A≥50(1-31/32")
B≥100(3-15/16")
C≥50(1-31/32")
D≥500(19-11/16")
A≥50(1-31/32")
B≥100(3-15/16")
C≥50(1-31/32")
D≥500(19-11/16")
E≥100(3-15/16")
A≥50(1-31/32")
B≥100(3-15/16")
C≥50(1-31/32")
D≥500(19-11/16")
E≥100(3-15/16")
F≥500(19-11/16")
A≥50(1-31/32")
B≥100(3-15/16")
C≥50(1-31/32")
D≥100(3-15/16")
E≥100(3-15/16")
F≥500(19-11/16")