Troubleshooting - Allen-Bradley 857-RAA User Manual

Rtd scanner
Table of Contents

Advertisement

Table 11 - Measurands that can be Assigned to Analog Outputs
XFault
Fault reactance
SagMin
Minimum voltage sag
Sagmax
Maximum voltage sag
U0
zero sequence voltage
AL1
Analog Input #1
AL2
Analog Input #2
AL3
Analog Input #3
AL4
Analog Input #4
Io1
Ground fault current channel 1
Io2
Ground fault current channel 2
Iocalc
Phasor sum IL1 + IL2 + IL3

Troubleshooting

ohms
Pu value of voltage
Pu value of voltage
Percentage of zero sequence setting
Scalable reading of AI1 (from 0...20mA)
Scalable reading of AI2 (from 0...20mA)
Scalable reading of AI3 (from 0...20mA)
Scalable reading of AI4 (from 0...20mA)
Ground Fault current #1
Ground Fault current #2
Phasor sum IL1 + IL2 + IL3
If an RTD sensor is disconnected (open circuited) a value of -200 ºC is
returned for the respective sensor channel. As well, a status indicator called
'Ext. Al disconnected' will be enabled within the Output Matrix of the base
857 relay.
If an RTD sensor is short circuited, a value of -250 ºC is returned for the
respective sensor channel. A status indicator called 'Ext. Al short circuit' will be
enabled within the Output Matrix of the base 857 relay.
If power is lost to the 857-RAA or if communications between the base relay
and the 857-RAA are lost:
• Each sensor channel displays a value of -250 ºC.
• There are two status indicators within the Output Matrix to provide
feedback on the communication link status to the RTD scanner.
'REMOTE Comm.' which is activated when the communication link to
the 857-RAA is active or 'REMOTE Comm Inactive' .
• Timeout counter increases in the Protocol menu
If power is lost to the 857-RAD or if communications between the base relay
and the 857-RAD is lost, when using Modbus RTU-protocol then:
• Each sensor channel value freezes
• AI error counter increases in the External analog inputs menu
• There are two status indicators within the Output Matrix to provide
feedback on the communication link status to the RTD scanner.
'EXTENSION Comm.' which is activated when the communication
link to the 857-RAD is active or 'EXTENSION Comm Inactive'
• Timeout counter increases in the Protocol menu
(1) If the application uses Remote or Extension-communication port, an alarm can be generated using relay logic, for example,
inverted Remote.comm – signal can be used to drive an LED indicator on the front of the relay.
Rockwell Automation Publication 857-UM002C-EN-P - February 2018
Configure the Base 857 Relay
Chapter 4
[Ω]
[pu]
[pu]
[%]
[mA]
[mA]
[mA]
[mA]
[A]
[A]
[A]
(1)
(1)
29