Configure the Base 857 Relay
20

RTD Inputs Quick Setup for 857-RAA

In the External I/O Configuration of SetPointPS, you will find RTD Inputs-
Quick Setup. This interface makes individual RTD channel setup quick and
simple.
Table 5 - RTD Inputs • Quick Setup Parameters
Parameter
Value(s)
AI Enabled
On / Off
RTD Ch
Cannot modify
RTD Sensor Type
Other..., Pt100, Ni100,
Ni120, Cu10
RTD Sensor
Off, WindingG, Bearing G,
Function
Ambient, Other...
(2)
Alarm Limit >
User-defined
(2)
Trip Limit >>
User-defined
(1) Only the first 12 channels are used for RTD inputs. Channels 13...16 only used with 857-RAD.
(2) Units are in Celsius.
IMPORTANT If a parameter is changed, it will be highlighted in red. This indicates that a
change has been made and this data must be uploaded into the base relay.
Once saved to the relay, the relay may request a reboot (restart) depending
on the setting changed.
Once all the settings for the 857-RAA have been completed, all these new
setting values must be uploaded into the relay by using the depressing the Write
All Settings to the Device icon within the SetPointPS software interface. See
publication 857-PM001. The alarm (start) and trip status information for each
channel enabled must be reviewed and mapped to an output device through
the Output Matrix in the 857 relay. See publication
the Output Matrix configuration.
Rockwell Automation Publication 857-UM002C-EN-P - February 2018
(1)
To Modify:
1. Select the row of the channel you want to modify.
2. Choose the desired selection from the pulldown menu.
N/A
1. Select the row of the channel you want to modify.
2. Choose the desired selection from the pulldown menu.
1. Select the row of the channel you want to modify.
2. Enter the desired value on your keyboard.
3. Press Enter.
857-UM001