Installation Guide - HB Products HBLC Instruction Manual

Sensor & controller for low and high pressure control of liquid levels in industrial refrigeration systems
Hide thumbs Also See for HBLC:
Table of Contents

Advertisement

The HBLC sensor also has a built-in controller. The parameters for controlling a modulating motor valve can
easily be set up in a configuration tool (HB Tool).
HBLC connected to a modulating valve – an alternative to low pressure float control.
An economiser with an HBLC connected to the modulating valve, type Siemens MVS661.

Installation Guide

The following applies to the design of the system:
1)
It must be mounted vertically.
2)
HBLC can be mounted on an overflow pipe or a pipe segment where flow and turbulence
are minimised.
3)
The sensor is installed with a standard cable without a sheath. If EMC is higher than
described in EN 61326, a sheathed cable must be used.