Lifting & Hanging Instructions - Greenheck MSCF Installation, Operation And Maintenance Manual

Modular small cabinet fan
Table of Contents

Advertisement

Lifting Instructions
Greenheck's Modular Small Cabinet Fan (MSCF) should be lifted by the factory supplied lifting
lugs or frame rails and a spreader bar to prevent damage from occurring to the equipment (see
figure 1). Avoid twisting or uneven lifting of equipment. Do not lift equipment by coil connections
or headers. The unit must remain upright during lifting. All access doors and panels must be
closed during lifting to avoid damage (see figure 1).
Figure 1
Hanging Instructions
The MSCF should be hung by the factory supplied lifting lugs or field supplied frame rails as
shown respectively in figures 2 and 3. The number of hanging brackets used will be determined
by the number of fan modules.
External Mounting Isolation
The MSCF is available with
both external neoprene and
spring isolation options. When
external isolation is selected a
bridge bracket will be
provided to reduce installation
time (see figure 4).
Spreader bar
Lifting lugs
Figure 2
HANGING BRACKET
PART NO. 710774
DRAWING NO. 85537
3/8-16x3/4 SPINLOCK BOLT
2 REQ'D PER ASSEMBLY
BRIDGE BRACKET
PART NO. 711779
DRAWING NO. 89814
1 REQ'D PER ASSEMBLY
3.00 in.
3/4" FLAT WASHER
1 REQ'D PER
ASSEMBLY
3/8-16 SPINLOCK NUT
2 REQ'D PER ASSEMBLY
BASE ASSEMBLY
3/4" FLAT WASHER
1 PER ASSEMBLY AS NEEDED
7
BRIDGE BRACKET
PART NO. 711779
DRAWING NO. 89814
LOCK BOLT
1 REQ'D PER ASSEMBLY
SSEMBLY
HANGING BRACKET
KET
PART NO. 710774
779
DRAWING NO. 85537
89814
ASSEMBLY
ER
HANGING ASSEMBLY
Figure 4
Frame Rails
(By others)
Figure 3
3/8-16x3/4 SPINLOCK BOLT
2 REQ'D PER ASSEMBLY
3/8-16 SPINLOCK NUT
2 REQ'D PER ASSEMBLY
3

Advertisement

Table of Contents
loading

Table of Contents