Download Print this page

Festo CTEU-AS Description, Installation And Interfaces page 3

Bus node

Advertisement

9
Technical data
General
Degree of protection through housing
(in accordance with EN 60529)
AS-interface specification
Protection against electric shock
(Protection against direct and indirect contact in
accordance with IEC/DIN 60204-1)
3)
Electromagnetic compatibility (EMC)
– emitted interference
– resistance to interference
Vibration and shock
(as per EN 60068)
– vibration (part 2 – 6)
– shock (part 2 – 27)
– continuous shock (part 2 – 29)
Temperature range
– storage/transport
– environment, operation
Materials
1) Requirement: Bus node mounted completely, plug connector in the plugged-in status or provided with
cover cap.
2) Note that connected devices may only satisfy a lower degree of protection, a smaller temperature
range, etc.
3) The bus node is intended for use in an industrial environment. Outside of industrial environments,
e.g. in commercial and mixed-residential areas, actions to suppress interference may have to be taken.
4) Explanation of the severity level
subsequent tables
Fig. 10
Vibration load
Frequency range [Hz]
Acceleration [m/s
Severity
SL2
SL1
level 1
2 ... 8
2 ... 8
8 ... 27
8 ... 27
10
27 ... 58
27 ... 60
58 ... 160
60 ... 160
20
160 ... 200
160 ... 200
10
Fig. 11
Shock load
2
Acceleration [m/s
]
Duration [ms]
SL1
SL2
SL1
±150
±300
11
Fig. 12
Continuous shock load
2
Acceleration [m/s
]
Duration [ms]
±150
6
Fig. 13
Power supply
AS-interface bus connection
– voltage range (protected against incorrect
polarity)
– residual ripple
AS-interface auxiliary power supply
– voltage range (protected against incorrect
polarity)
– residual ripple
Intrinsic current consumption
– bus node electronics
– bus node on device (e.g. valve terminal)
– bus node on electrical connecting plate
CAPC-...
Load current for the AS-interface slave
Fig. 14
Technical data of the connected equipment can be found in the respective
product documentation.
1) 2)
IP65/67
3.0
Through use of PELV circuits
See declaration of conformity
www.festo.com
4)
Severity level (SL)
for mounting on
Wall: SG 2, H-rail: SG 1
Wall: SG 2, H-rail: SG 1
Wall and H-rail: SG 1
2)
–20 ... +70 °C
2)
–5 ... +50 °C
PA (reinforced), PC, NBR, steel (galvanized),
RoHS-compliant circuit boards
2
]
Deflection [mm]
SL2
SL1
SL2
±3.5
±7
10
±0.15
±0.75
50
10
Shocks per direction
SL2
SL1
SL2
11
5
5
Shocks per direction
1000
26.5 ... 31.6 V DC
š20 mVpp
24 V DC _10%
4 mVpp
Max. 30 mA
Max. 60 mA
Max. 30 mA
Max. 700 mA
(A load of max. 700 mA can be connected to
the "AS-interface Out" socket.)

Advertisement

loading