Gree GMV-ND22PHS/B-T Owner's Manual page 13

Super high static pressure duct type indoor unit
Hide thumbs Also See for GMV-ND22PHS/B-T:
Table of Contents

Advertisement

in order to drain condensation water smoothly.
(2) The diameter of drainage hose should be bigger or equal to the diameter of drainage pipe
joint.
(3) Install drainage pipe according to the following fig and arrange insulation to the drainage
pipe. Improper installation may lead to water leakage and damp the furniture and other
things in the room.
(4) You can buy normal hard PVC pipe used as the drainage pipe. During connection, insert
the end of PVC pipe into the drainage hole and then tighten it with drainage hole and wire
binder. Can't connect the drainage hole and drainage hole with glue.
(5) When the drainage pipelines are used for several units, the position of pipeline should be
about 100mm lower than the drainage port of each unit. In this case, thicker pipes should
be applied.
4.3.2 Drainage Pipe Installation
(1) Insert the drain hose into the drain hole and tighten it with tapes, as shown in Fig 4.3.2.
(2) Tighten the pipe clamp, with the distance between screw nut and hose smaller than 4mm.
① metal clamp(accessory)
② drain hose(accessory)
(3) Use sealing plate to make the pipe clamp and hose insulated, as shown in Fig.4.3.3.
① metal clamp(accessory)
②thermal sponge(accessory)
(4) When connecting several drain pipes, follow the instruction as indicated in Fig 4.3.4.
Choose the drain collecting pipe that matches with unit capacity.
(5) If the negative pressure at the outlet of drainage pipe is big, the drainage pipe of indoor
unit must adopt U-trap elbow.
Multi Variable Air Conditioners Ducted Type Indoor Unit
Fig 4.3.1
Fig 4.3.2
Fig 4.3.4
10
Fig 4.3.3

Advertisement

Table of Contents
loading

Table of Contents