The Pocket Portable Configurator type PPC1090 is suitable to configure the "smart" barrier of D1000 series. The PPC1090 unit is not ATEX, UL or FM approved and is only to be used in
Safe Area/Non Hazardous Locations and prior to installation of the isolator and prior to connection of any I.S. wiring. Do not use PPC1090 configurator in Hazardous Area/Hazardous
Locations. The PPC1090 configurator is powered by the unit (no battery power) when the telephone jack is plugged into the barrier (RJ12 6 poles connection type with 1:1 connection).
It has a 5 digit display, 4 leds and four push buttons with a menu driven configuration software and can be used in Safe Area/Non Hazardous Locations without any certification because
it plugs into the non intrinsically safe portion of circuit.
The configuration procedure follows a unit specific menu. The display shows the actual menu item, the led shows the channel configured and the push button actuates as "Enter",
"Select", "Down" and "Up" key. The "Enter" key is pressed to confirm the menu item, the "Select" key is pressed to scroll the menu item, the "Down" and "Up" keys are pressed to
decrement or increment the numeric value of menu item. The "Up" key is also pressed to decrement the menu level. When the PPC1090 is plugged into the unit, the display shows the
barrier model (first level menu). Then press the "Enter" key to the second level menu and the "Select" key to scroll the menu voice. When the selected menu item is displayed press the
"Enter" key to confirm the choice. Follow this procedure for every voice of the menu. When a numeric menu item is to be changed, press the "Select" key to highlight the character and
then the "Up" and "Down" keys to select the number; confirm the modification with the "Enter" key. To return to a higher level menu press the "Up" key.
D1073S Menu
1)
2)
3)
4)
5)
6)
7)
8)
9)
G.M. International ISM0019-13
PPC1090 Configuration
D1073S
[1 Level Menu]
Displays Model D1073S single channel temperature signal converter and trip amplifiers. Press "Enter" key to second level menu.
CF
[2 Level Menu]
Displays the parameters configuration menu. Press "Enter" key to configure the functional parameters, press the "Select" key to the next menu
level item or "Up" key to return to first level.
In
[2 Level Menu]
Displays the input variable monitoring. Press "Enter" to display the current input value reading, press the "Select" key to the next menu level
item or "Up" key to return to first level.
Out
[2 Level Menu]
Displays the analog output variable monitoring. Press "Enter" to display the current output value reading, press the "Select" key to the next
menu level item or "Up" key to return to first level.
Set A
[3 Level Menu]
Displays the SET A Trip Point Value configuration. Press "Enter" to set the trip point value, press the "Select" key to the next menu level item or
"Up" key to return to second level. If you pressed "Enter" key, you can set the set value; press the "Select" key to highlight the character you
want to change and then the "Up" and "Down" keys to select the number; confirm the modification with the "Enter" key
Set B
[3 Level Menu]
Displays the SET B Trip Point Value configuration. Press "Enter" to set the trip point value, press the "Select" key to the next menu level item or
"Up" key to return to second level. If you pressed "Enter" key, you can set the set value; press the "Select" key to highlight the character you
want to change and then the "Up" and "Down" keys to select the number; confirm the modification with the "Enter" key
Sens
[3 Level Menu]
Displays the input sensor type configuration. Press "Enter" to set the input sensor, press the "Select" key to the next menu level item or "Up" key
to return to second level. If you pressed "Enter" key, you can choose between 26 different sensors; press "Select" key to change the input
sensor and then the "Enter" key to confirm the choice. The input sensors are:
Tc B
Thermocouple type B, -10 to +1800°C range
Tc E
Thermocouple type E, -250 to +1000°C range
Tc J
Thermocouple type J, -200 to +750°C range
Tc K
Thermocouple type K, -250 to +1350°C range
Tc L
Thermocouple type L, -200 to +800°C range
Tc N
Thermocouple type N, -200 to +1300°C range
Tc R
Thermocouple type R, -50 to +1750°C range
Tc S
Thermocouple type S, -50 to +1750°C range
Tc T
Thermocouple type T, -250 to +400°C range
Tc U
Thermocouple type U, -200 to +400°C range
Tc LR
Thermocouple type LR (russian standard), -200 to +800°C range
Pt 100
Thermoresistance Pt 100 Ω with 0.385 coefficient, -200 to +850°C range
PP 100
Thermoresistance Pt 100 Ω with 0.392 coefficient, -200 to +625°C range
M 100
Thermoresistance Pt 100 Ω with 0.391 coefficient (russian standard), -200 to +650°C range
M 50
Thermoresistance Pt 50 Ω with 0.391 coefficient (russian standard), -200 to +650°C range
Ni 100
Thermoresistance Ni 100 Ω, -50 to +180°C range
Ni 120
Thermoresistance Ni 120 Ω, (russian standard), -75 to +300°C range
CU 100
Thermoresistance Copper 100 Ω (russian standard), -50 to +200°C range
CU 53
Thermoresistance Copper 53 Ω (russian standard), -50 to +180°C range
CU 50
Thermoresistance Copper 50 Ω (russian standard), -50 to +200°C range
Pot
Potentiometer, 0 to 100% range
E dc
mV dc input from externally powered transmitter, -20 to +85mV range
Pt 200
Thermoresistance Pt 200 Ω with 0.385 coefficient, -150 to +400°C range
Pt 300
Thermoresistance Pt 300 Ω with 0.385 coefficient, -150 to +250°C range
Tc A1
Thermocouple type A1 (russian standard), -10 to +2500°C range
Tc A2
Thermocouple type A2 (russian standard), -10 to +1800°C range
Tc A3
Thermocouple type A3 (russian standard), -10 to +1800°C range
Tc S1
Thermocouple type S (russian standard), -50 to +1600°C range
CU 46
Thermoresistance Copper 46 Ω (russian standard), -200 to +650°C range
Lead
[3 Level Menu]
Displays the input sensor connection type configuration for thermoresistance sensor. Press "Enter" to set the input connection type, press the
"Select" key to the next menu level item or "Up" key to return to second level. If you pressed "Enter" key, you can choose between 2 different
sensor connection; press "Select" key to change the input connection and then the "Enter" key to confirm the choice. The input connection types are:
3 ter
3 wire connection type thermoresistance
4 ter
4 wire connection type thermoresistance
CJ Typ
[3 Level Menu]
Displays the reference junction compensation type configuration for thermocouple sensor. Press "Enter" to set the input compensation type,
press the "Select" key to the next menu level item or "Up" key to return to second level. If you pressed "Enter" key, you can choose between 2
different sensor compensation types; press "Select" key to change the type and then the "Enter" key to confirm the choice.
The input compensation types are:
CJ Aut
automatic compensation of ambient temperature (via option 91 thermoresistance sensor)
CJ Set
fixed ambient temperature compensation, value is setted by CJ Ref menu item (do not require option 91 thermoresistance sensor)
D1073 - SIL 2 Temperature Signal Converter and Trip Amplifiers