In the system safety analysis, always check the Hazardous Area/Hazardous Locations devices to conform with the related system documentation, if the device is Intrinsically Safe check
its suitability for the Hazardous Area/Hazardous Locations and gas group encountered and that its maximum allowable voltage, current, power (Ui/Vmax, Ii/Imax, Pi/Pi) are not exceeded
by the safety parameters (Uo/Voc, Io/Isc, Po/Po) of the D1073 Associated Apparatus connected to it. Also consider the maximum operating temperature of the field device, check that
added connecting cable and field device capacitance and inductance do not exceed the limits (Co/Ca, Lo/La, Lo/Ro) given in the Associated Apparatus parameters for the effective gas
group. See parameters on enclosure side and the ones indicated in the table below:
D1073 Terminals
Ch1
13 - 14 - 15 - 16
Ch1
13 - 14 - 15 - 16
Ch1
13 - 14 - 15 - 16
D1073 Terminals
Ch1
13 - 14 - 15 - 16
Ch1
13 - 14 - 15 - 16
Ch1
13 - 14 - 15 - 16
When used with separate powered intrinsically safe devices, check that maximum allowable voltage (Ui/Vmax) of the D1073 Associated Apparatus are not exceeded by the safety
parameters (Uo/Voc) of the Intrinsically Safe device, indicated in the table below:
D1073 Terminals
Ch1 13 - 14 - 15 - 16
Ch1 13 - 14 - 15 - 16
For installations in which both the Ci and Li of the Intrinsically Safe apparatus exceed 1 % of the Co and Lo parameters of the Associated Apparatus (excluding the cable),
then 50 % of Co and Lo parameters are applicable and shall not be exceeded (50 % of the Co and Lo become the limits which must include the cable such that
Ci device + C cable ≤ 50 % of Co and Li device + L cable ≤ 50 % of Lo).
If the cable parameters are unknown, the following value may be used: Capacitance 60pF per foot (180pF per meter), inductance 0.20µH per foot (0.60µH per meter).
The Intrinsic Safety Entity Concept allows the interconnection of Intrinsically Safe devices approved with entity parameters not specifically examined in combination as a system
when the above conditions are respected.
For Division 1 and Zone 0 installations, the configuration of Intrinsically Safe Equipment must be FM approved under Entity Concept (or third party approved);
for Division 2 installations, the configuration of Intrinsically Safe Equipment must be FM approved under non-incendive field wiring or Entity Concept (or third party approved).
4
D1073 - SIL 2 Temperature Signal Converter and Trip Amplifiers
Parameters Table
D1073 Associated
Apparatus Parameters
Uo / Voc = 10.8 V
Io / Isc = 9 mA
Po / Po = 24 mW
D1073 Associated
Apparatus Parameters
Co / Ca = 2.134 µF
(IIC-A, B)
(IIB-C)
Co / Ca = 14.994 µF
Co / Ca = 65.994 µF
(IIA-D)
(IIC-A, B)
Lo / La = 468 mH
Lo / La = 1874 mH
(IIB-C)
(IIA-D)
Lo / La = 3749 mH
Lo / Ro = 1510 µH/Ω
(IIC-A, B)
(IIB-C)
Lo / Ro = 6050 µH/Ω
Lo / Ro = 12100 µH/Ω
(IIA-D)
NOTE for USA and Canada:
IIC equal to Gas Groups A, B, C, D, E, F and G
IIB equal to Gas Groups C, D, E, F and G
IIA equal to Gas Groups D, E, F and G
D1073 Associated
Apparatus Parameters
Ui / Vmax = 18 V
Ci = 6 nF, Li= 0 nH
Hazardous Area/
Must
Hazardous Locations
be
Device Parameters
Ui / Vmax
Ii/ Imax
Pi / Pi
Hazardous Area/
Must
Hazardous Locations
be
Device + Cable Parameters
Ci / Ci device + C cable
Li / Li device + L cable
Li / Ri device and
L cable / R cable
Hazardous Area/
Must
Hazardous Locations
be
Device Parameters
Uo / Voc
G.M. International ISM0019-13