Technical Data - G.M. International D1073S Instruction Manual

Sil 2 temperature signal converter, and trip amplifiers din-rail
Table of Contents

Advertisement

For Safety Related System and SIL2, SIL3 Applications according IEC61508 & IEC61511 Standards refer to "Functional Safety Manual" document number ISM0071
General Description: The single channel DIN Rail Temperature Signal Converter and Trip Amplifier D1073S accepts a low level dc signal from millivolt, thermocouple or RTD
temperature sensor, located in Hazardous Area, and converts, with isolation, the signal to drive a Safe Area load. Output signal can be direct or reverse. Two independent Alarm Trip
Amplifiers are also provided. Each alarm energizes, or de-energizes, an SPST relay for high, low, low-startup or burnout alarm functions. The two alarm relays trip points are settable
over the entire input signal range.
Function: 1 channel I.S. input from mV, thermocouples, 3-4 wires resistance thermometers, transmitting potentiometers, provides 3 port isolation (input/output/supply) and current
(source mode) or voltage output signal. The programmable RTD line resistance compensation allows the use of 2 wires RTDs or error compensation for 3-4 wires RTDs.
Reference junction compensation can be automatic, with option 91, or fixed by software setting. In addition it provides two SPST relay alarm contacts with adjustable alarm trip point.
Signalling LEDs: Power supply indication (green), burnout (red), alarm A (red), alarm B (red).
Configurability: Totally software configurable, no jumpers or switches, input sensor, connection mode, burnout operation, mA or V output signal, alarm trip point, high, low, low-startup
or burnout alarm mode, NE/ND relay operation, hysteresis, delay time, by GM Pocket Portable Configurator PPC1090, powered by the unit or configured by PC via RS-232 serial line
with PPC1092 Adapter and SWC1090 Configurator software. A 16 characters tag can be inserted using SWC1090 Configurator software.
EMC: Fully compliant with CE marking applicable requirements.
Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current consumption @ 24 V: 65 mA with 20 mA output and relays energized typical.
Power dissipation: 1.5 W with 24 V supply, 20 mA output and relays energized typical.
Max. power consumption: at 30 V supply voltage, overload condition, relays energized and PPC1090 connected, 2.1 W.
Isolation (Test Voltage): I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV.
Input: millivolt or thermocouple type A1, A2, A3, B, E, J, K, L, Lr, N, R, S, S1, T, U or 3-4 wires RTD Pt100, Pt200, Pt300 to DIN43760, Pt100 (0.3916), Ni100, Ni120 or
Pt500, Pt100, Pt50, Cu100, Cu53, Cu50, Cu46 (russian standard) or 3 wires transmitting potentiometer (50 Ω to 20 KΩ).
Integration time: 500 ms.
Resolution: 5 µV on mV or thermocouple, 1 µV thermocouple type B, R, S, S1, 2 µV thermocouple A1, A2, A3, 20 mΩ on RTD, 0.05 % on transmitting potentiometer.
Visualization: 0.1 °C on temperature, 10 µV on mV, 0.1 % on potentiometer.
Input range: within rated limits of sensor (-10 to + 80 mV).
Measuring RTD current: ≤ 0.5 mA.
RTD line resistance compensation: ≤ 10 Ω.
RTD line resistance error compensation: - 5 to + 20 Ω, programmable.
Thermocouple Reference Junction Compensation: automatic, by external sensor OPT91 separately ordered, or fixed programmable from - 60 to + 100 °C.
Thermocouple burnout current: ≤ 30 nA.
Burnout: enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. Burnout condition signalled by red front panel LED.
Alarms can be programmed to detect burnout condition.
Output: 0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Resolution: 2 µA current output or 1 mV voltage output.
Transfer characteristic: linear or reverse on mV or transmitting potentiometer, temperature linear or reverse on temperature sensors.
Response time: ≤ 50 ms (10 to 90 % step change).
Output ripple: ≤ 20 mVrms on 250 Ω load.
Alarm:
Trip point range: within rated limits of input sensor (see input for step resolution).
ON-OFF delay time: 0 to 1000 s, 100 ms step, separate setting.
Hysteresis: 0 to 5 °C for temperature sensor input, 0 to 50 mV for mV input, 0 to 50 % for potentiometer input (see input for step resolution).
Output: voltage free SPST relay contact.
Contact rating: 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
Performance: Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Input:
Calibration and linearity accuracy: ≤ ± 40 µV on mV or thermocouple, 200 mΩ on RTD, 0.2 % on potentiometer or ± 0.05 % of input value.
Temperature influence: ≤ ± 2 µV, 20 mΩ, 0.02 % or ± 0.01 % of input value for a 1 °C change.
Ref. Junction Compensation influence: ≤ ± 1 °C (thermocouple sensor).
Analog Output:
Calibration accuracy: ≤ ± 0.1 % of full scale.
Linearity error: ≤ ± 0.05 % of full scale.
Supply voltage influence: ≤ ± 0.05 % of full scale for a min to max supply change.
Load influence: ≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
Compatibility:
CE mark compliant, conforms to 94/9/EC Atex Directive and to 2004/108/CE EMC Directive.
Environmental conditions: Operating: temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Storage: temperature limits – 45 to + 80 °C.
Safety Description:
II (1) G [Ex ia Ga] IIC, II (1) D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I, II 3G Ex nA IIC T4, [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I associated electrical apparatus.
Uo/Voc = 10.8 V, Io/Isc = 9 mA, Po/Po = 24 mW at terminals 13-14-15-16.
Ui/Vmax = 18 V, Ci = 6 nF, Li = 0 nH at terminals 13-14-15-16.
Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
Approvals: DMT 01 ATEX E 042 X conforms to EN60079-0, EN60079-11, EN60079-26, EN61241-0, EN61241-11,
IECEx BVS 07.0027X conforms to IEC60079-0, IEC60079-11, IEC60079-26, IEC61241-0, IEC61241-11, GM International CRR028 conforms to EN60079-0, EN60079-15,
UL & C-UL E222308 conforms to UL913 (Div.1), UL 60079-0 (General, All Zones), UL60079-11 (Intrinsic Safety "i" Zones 0 & 1) for UL and
CSA-C22.2 No.157-92 (Div.1), CSA-E60079-0 (General, All Zones), CSA-E60079-11 (Intrinsic Safety "i" Zones 0 & 1) for C-UL,
refer to control drawing ISM0142 for complete UL and C-UL safety and installation instructions,
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3610, 3611, 3810 and C22.2 No.142, C22.2 No.157, C22.2 No.213, E60079-0, E60079-11, E60079-15,
Russia according to GOST 12.2.007.0-75, R 51330.0-99, R 51330.10-99 [Exia] IIC X, Ukraine according to GOST 12.2.007.0,22782.0,22782.5 Exia IIC X,
TUV Certificate No. C-IS-204194-02, SIL 2 according to IEC 61508, IEC 61511. Please refer to Functional Safety Manual for SIL applications.
DNV and KR Type Approval Certificate for marine applications.
Mounting: T35 DIN Rail according to EN50022.
Weight: about 160 g.
Connection: by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm
Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA
T4 installation.
Protection class: IP 20.
Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
2
D1073 - SIL 2 Temperature Signal Converter and Trip Amplifiers
SIL Applications
Characteristics

Technical Data

.
2
G.M. International ISM0019-13