G.M. International D1073S Instruction Manual page 10

Sil 2 temperature signal converter, and trip amplifiers din-rail
Table of Contents

Advertisement

10)
CJ Ref
Displays the ambient temperature compensation value configuration for thermocouple sensor. Press "Enter" to set the value, press the "Select"
key to the next menu level item or "Up" key to return to second level. If you pressed "Enter" key, you can set the compensation value; press the
"Select" key to highlight the character you want to change and then the "Up" and "Down" keys to select the number; confirm the modification with
the "Enter" key. The value is settable from –60 to +100 °C
11)
Rt Lin
Displays the thermoresistance compensation value configuration for thermoresistance sensor. Press "Enter" to set the value, press the "Select"
key to the next menu level item or "Up" key to return to second level. If you pressed "Enter" key, you can set the compensation value; press the
"Select" key to highlight the character you want to change and then the "Up" and "Down" keys to select the number; confirm the modification
with the "Enter" key. The value is settable from –5 to +20 Ω
12)
Out
Displays the analog output type configuration. Press "Enter" to set the analog output type and range, press the "Select" key to the next menu level item or "Up" key to return to
second level. If you pressed "Enter" key, you can choose between 6 different output types; press "Select" key to change the output type and range and then the "Enter" key to
confirm the choice. The output types are:
4-20
4 to 20 mA current output
0-20
0 to 20 mA current output
1-5
1 to 5 V voltage output
0-5
0 to 5 V voltage output
2-10
2 to 10 V voltage output
0-10
0 to 10 V voltage output
13)
Dn Sc
Displays the input low scale configuration. Press "Enter" to set the low scale input value, press the "Select" key to the next menu level item or "Up" key to return to second
level. If you pressed "Enter" key, you can set the low input value; press the "Select" key to highlight the character you want to change and then the "Up" and "Down" keys to
select the number; confirm the modification with the "Enter" key. The value is settable over the entire range of the sensor as specified.
14)
Up Sc
Displays the input high scale configuration. Press "Enter" to set the high scale input value, press the "Select" key to the next menu level item or "Up" key to return to second
level. If you pressed "Enter" key, you can set the high input value; press the "Select" key to highlight the character you want to change and then the "Up" and "Down" keys to
select the number; confirm the modification with the "Enter" key. The value is settable over the entire range of the sensor as specified.
15)
Burn
Displays the burnout configuration. Press "Enter" to set the burnout condition, press the "Select" key to the next menu level item or "Up" key to return to second level.
If you pressed "Enter" key, you can choose between 3 different burnout conditions; press "Select" key to change the burnout and then the "Enter" key to confirm the choice.
The condition types are:
none
no burnout detection, the analog output follows the input value
br dn
when in burnout condition, the analog output goes to down scale (0 mA or 0 V)
br up
when in burnout condition, the analog output goes to high scale (22 mA or 11 V)
16)
Alr A / Alr B
Displays the Alarm A / Alarm B configuration menu. Press "Enter" to set the alarm condition, press the "Select" key to the next menu level item or "Up" key to return to second level.
17)
Type
Displays the alarm type (A or B) configuration. Press "Enter" to set the alarm condition, press the "Select" key to the next menu level item or "Up" key to return to third level.
If you pressed "Enter" key, you can choose between 5 different alarm conditions; press "Select" key to change the type and then the "Enter" key to confirm the choice.
The condition types are:
OFF
no alarm detection, the relay output is always in normal condition
HI
high alarm condition, the relay output change status when an alarm condition is detected (input variable goes above the set value)
LO
low alarm condition, the relay output change status when an alarm condition is detected (input variable goes below the set value)
LOSEC
low with start-up alarm condition, the relay output change status when an alarm condition after the start-up is detected (input variable starts below the set
value but no alarm condition is signaled, after the warm-up the variable goes above the set value arming the alarm detection, then when the variable goes
below the set value the alarm condition is signaled)
BURN
burnout alarm condition, the alarm condition change status when a burnout condition appear in the input sensor.
18)
B Ope
Displays the functionality of alarm in burnout condition (A or B) configuration. Press "Enter" to set the burnout alarm condition, press the "Select" key to the next menu level
item or "Up" key to return to third level. If you pressed "Enter" key, you can choose between 4 different alarm burnout conditions; press "Select" key to change the type and
then the "Enter" key to confirm the choice. The types are:
OFF
the alarm goes in disabled condition when a burnout is detected
NOR
the alarm follow the condition of input variable (not relevant burnout)
LOCK
the alarm is locked in the same position as before a burnout is detected
ON
the alarm goes in enabled condition when a burnout is detected
Note that a minimum of 1 second delay ("On dl" item) is necessary to obtain the burnout detection on alarm conditions.
19)
Relay
Displays the relay normal condition (A or B) configuration. Press "Enter" to set the relay condition, press the "Select" key to the next menu level item or "Up" key to return to
third level. If you pressed "Enter" key, you can choose between 2 different relay conditions; press "Select" key to change the type and then the "Enter" key to confirm the
choice. The condition types are:
ND
relay normally de-energized (energized in alarm condition)
NE
relay normally energized (de-energized in alarm condition)
20)
Hyst
Displays the alarm hysteresis value (A or B) configuration. Press "Enter" to set the deadband value, press the "Select" key to the next menu level item or "Up" key to return to
third level. If you pressed "Enter" key, you can set the hysteresis value (engineering value); press the "Select" key to highlight the character you want to change and then the
"Up" and "Down" keys to select the number; confirm the modification with the "Enter" key. The value is settable from 0 to 5000 points regarding the input sensor as specified.
21)
On dly
Displays the alarm activation delay (A or B) configuration. Press "Enter" to set the delay time value, press the "Select" key to the next menu level item or "Up" key to return to
third level. If you pressed "Enter" key, you can set the delay value (100 ms step); press the "Select" key to highlight the character you want to change and then the "Up" and
"Down" keys to select the number; confirm the modification with the "Enter" key The value is settable from 0 to 1000 seconds in steps of 100 ms.
22)
OF dly
Displays the alarm de-activation delay (A or B) configuration. Press "Enter" to set the delay time value, press the "Select" key to the next menu level item or "Up" key to return
to third level. If you pressed "Enter" key, you can set the delay value (100 ms step); press the "Select" key to highlight the character you want to change and then the "Up" and
"Down" keys to select the number; confirm the modification with the "Enter" key The value is settable from 0 to 1000 seconds in steps of 100 ms.
10
D1073 - SIL 2 Temperature Signal Converter and Trip Amplifiers
[3 Level Menu]
[3 Level Menu]
[3 Level Menu]
[3 Level Menu]
[3 Level Menu]
[3 Level Menu]
[3 Level Menu]
[4 Level Menu]
[4 Level Menu]
[4 Level Menu]
[4 Level Menu]
[4 Level Menu]
[4 Level Menu]
G.M. International ISM0019-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents