Raychem TRACETEK TTC-1 Installation, Operation And Maintenance Instructions

Raychem TRACETEK TTC-1 Installation, Operation And Maintenance Instructions

Sensing module

Advertisement

Quick Links

TTC-1
TraceTek Sensing Module Installation, Operation
and Maintenance Instructions
2 in
(52 mm)
TRACETEK
4.4 in
(112 mm)
Figure 1: TTC-1 Module
IMPORTANT NOTES
• The TTC-1 module is designed for use with TraceTek sensing
cables and probes only. A TTC-1 based system will detect and
alarm on all fluid leaks detected by the TraceTek cable as per
the appropriate cable data sheet.
• Transient spills and contamination may also activate the
system. Users should consider this operational function when
determining the suitability of the TraceTek system for specific
applications.
• The system has not been designed for repetitive cycling.
• Always connect the Leak Detection relay to an annunciation
device (for example the nVent RAYCHEM TraceTek TTE-XAL
External Loud Alarm) so that an operator is notified and can
verify proper operation if automatic equipment is connected.
• Maintenance personnel should examine the sensing cable for
cleanliness and verify proper operation of the TTC-1 module at
least every six (6) months.
4.2 in
(106 mm)
DESCRIPTION
The nVent RAYCHEM TraceTek TTC-1 sensing module is used with
TraceTek sensing cables to detect liquid leaks. The module provides
visual indication when a leak or cable break has occurred and has
relay contacts to connect the TTC-1 to external devices for remote
monitoring and control.
ELECTRICAL CODES
Installation must be done in accordance with national and local
codes and regulations that apply. The TTC-1 must be installed in
ordinary areas only.
MODULE LOCATION
Enclosure rating: IP 20 / NEMA 1
Operating temperature range: 0ºC to 50ºC (32ºF to 122ºF)
SPECIFICATIONS
Maximum sensing cable length: 250 ft (76 m)
• Leader cable length is not included in the length limitation.
Input power:
• 12 to 24 Volts AC – 0.25 A
• 15 to 24 Volts DC – 0.15 A
• When using a transformer, use UL listed Class II transformer
rated at 24 V, 20 VA
Recommended fuse rating: 3 A
Relay ratings: 3 A: 30 Volts DC or 24 Volts AC
INSTALLATION MATERIALS AND TOOLS REQUIRED
Wall fastener (2 ea for surface mounting only)
PARTS AND MATERIALS
• 1 ea TTC-1 Sensing Module
• 1 ea TTC-1 Wall Label
• 4 ea Strain Reliefs
OPTIONAL ACCESSORIES
• TTC-DRC DIN Rail Clip – Part # 062825-000
• TTE-XAL External Loud Alarm – Part # 418569-000
• TT-MAP-TOOL – Part # E43135-000
APPROVALS
TYPE NM
General Signaling Equipment
76LJ

Advertisement

loading
Need help?

Need help?

Do you have a question about the TRACETEK TTC-1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Raychem TRACETEK TTC-1

  • Page 1 TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION The nVent RAYCHEM TraceTek TTC-1 sensing module is used with TraceTek sensing cables to detect liquid leaks. The module provides visual indication when a leak or cable break has occurred and has relay contacts to connect the TTC-1 to external devices for remote monitoring and control.
  • Page 2 Installing the TTC-1 Preparation for Mounting Open the knockouts as required on the base unit. The holes are sized for the PG-9 threaded strain relief provided in the kit. For DIN 1 Rail Mounting For Wall Mounting TTC-DRC TTC-1 Attach the optional rail Mounting Use the two holes in the holes 85mm...
  • Page 3 Power Supply Connection Relay Connections Note: For proper operation of the TTC-1, use a power Trouble Relay: supply whose output is electrically isolated from the One relay with single pole, double throw contact. incoming AC line power and ground. The relay is normally energized. Loss of power at the TTC-1 module One (and only one) TTC-1 can be connected to the output of causes the relay to switch to the ALARM condition (COM-NC open).
  • Page 4 Operating Instructions System Operation The TTC-1 module and attached sensor cable continuously monitors TRACETEK for liquid contact and wire breakage. LEDs on the cover of the enclosure indicate the status of the system, see Figure 8. Relay contacts react to leak detection as well as trouble conditions: Normal Mode Indications: LEAK LED CABLE BREAK LED...
  • Page 5: Sensitivity Adjustment

    1. Normal Operation: Look for Green POWER LED relay from activating on short term transient conditions caused 2. Leak Simulation: For systems using nVent RAYCHEM by air conditioner start-up. The factory default setting is zero TraceTek TT1000 or TT3000 sensor cable, use a TraceTek delay.
  • Page 6: Troubleshooting Guide

    Action: Check the sensor cable for possible pinch points. nVent front panel. Heavily contaminated cable may require replacement. RAYCHEM TraceTek TT5000 and TT5001 can be tripped if tightly Sensitivity can be adjusted to a lower level, but if dirt is accumulating, bent or compressed by a heavy object.