Unipower 103-3002 Series User's Product Manual

Float current battery monitor +24/-48 vdc
Table of Contents

Advertisement

Quick Links

SAGEON VIGIL
F
C
LOAT
URRENT
B
M
ATTERY
ONITOR
P
M
F
RODUCT
ANUAL
OR
103-3002-XX +24/-48 Vdc Model
UNIPOWER, LLC
3900 Coral Ridge Drive
Coral Springs, FL 33065
Phone: +1- 954-346-2442
Toll Free: 1-800-440-3504
PM990-3002-00, Issue 3
Web site –
http://www.unipowerco.com

Advertisement

Table of Contents
loading

Summary of Contents for Unipower 103-3002 Series

  • Page 1 SAGEON VIGIL LOAT URRENT ATTERY ONITOR RODUCT ANUAL 103-3002-XX +24/-48 Vdc Model UNIPOWER, LLC 3900 Coral Ridge Drive Coral Springs, FL 33065 Phone: +1- 954-346-2442 Toll Free: 1-800-440-3504 PM990-3002-00, Issue 3 Web site – http://www.unipowerco.com...
  • Page 2 *SAVE ALL SHIPPING MATERIAL FOR THE INSPECTOR TO SEE! After the inspection has been made, call UNIPOWER. We will determine if the equipment should be returned to our plant for repair, or if some other method would be more expeditious. If it is determined that the equipment should be returned to UNIPOWER, ask the delivering carrier to send the packages back to UNIPOWER at the delivering carrier's expense.
  • Page 3 SAGEON VIGIL PRODUCT MANUAL NAMEPLATE Each piece of UNIPOWER equipment is identified by a part number on the nameplate. Please refer to this number in all correspondence with UNIPOWER. INITIAL SETTINGS All equipment is shipped from our production area fully checked and adjusted.
  • Page 4 UNIPOWER, LLC SAGEON VIGIL Monitor/Controller. PROPRIETARY AND CONFIDENTIAL The information contained in this product manual is the sole property of UNIPOWER, LLC. Reproduction of the manual or any portion of the manual without the written permission of UNIPOWER, LLC is prohibited.
  • Page 5: Table Of Contents

    SAGEON VIGIL PRODUCT MANUAL TABLE OF CONTENTS INTRODUCTION ....................... 1-1 GENERAL DESCRIPTION ....................... 1-1 FEATURES ..........................1-1 SPECIFICATIONS ........................1-2 1.3.1 Physical Specifications ......................1-2 1.3.2 Environmental Specifications (each, VIGIL and Expansion) ..........1-2 1.3.3 Electrical Specifications (each, VIGIL and Expansion) ............1-3 1.3.4 General Plant Performance Specifications ................
  • Page 6 SAGEON VIGIL PRODUCT MANUAL SYSTEM OPTIONS MENU ....................3-18 3.8.1 System Password Sub-Menu ..................... 3-18 3.8.2 Negative Volts Sub-Menu ....................3-18 3.8.3 Negative Amps Sub-Menu ....................3-19 3.8.4 Temperature Inputs Sub-Menu ..................3-19 3.8.5 Idle Display Sub-Menu ...................... 3-19 3.8.6 Audible Alarm Sub-Menu ....................
  • Page 7 SAGEON VIGIL PRODUCT MANUAL TABLE OF ABBREVIATIONS ABBREVIATION, ACRONYM OR SYMBOL MEANING ANSI American National Standards Institute American wire gauge controlled environment vault circular mils CEMF Counter Electro-motive Force dual in-line package electromagnetic interference electrostatic discharge +48-volt fuse and breaker alarm high voltage alarm HVSD high voltage shutdown...
  • Page 8 SAGEON VIGIL PRODUCT MANUAL TABLE OF REFERENCES DOCUMENT TITLE NUMBER ANSI C 39.1 Requirements for Electrical Analog Indicating Instruments ANSI T1.311-1991 DC Power Systems – Telecommunications Environment Protection ANSI/IEEE C 62.41- IEEE Guide for Surge Voltages in Low-Voltage AC Power Circuits, 1980 ANSI IEC 801-2...
  • Page 9: Introduction

    The SAGEON VIGIL was designed to be a compact and easy way to monitor the status of your batteries. It was designed to be used in conjunction with the UNIPOWER Float Charging Current Probes (FCCP) to monitor the float current of your batteries. The SAGEON VIGIL has...
  • Page 10: Specifications

    SAGEON VIGIL PRODUCT MANUAL • Front panel LED alarm indicators: (Red) MAJOR, FA, VLVA, LVD, HVSD, CUR/WD, RFA, & TA; (Yellow) MINOR, LVA, CEMF, HVA, ACO, EQ, CTRL-INH, and (Green) Power • Audible alarm with a user selectable trigger point and cut-out durations •...
  • Page 11: Electrical Specifications (Each, Vigil And Expansion)

    SAGEON VIGIL PRODUCT MANUAL 1.3.3 Electrical Specifications (each, VIGIL and Expansion) Power/Supply Input: +24 Vdc @ 400 mA (worst case) -48 Vdc @ 200 mA (worst case) Maximum Supply Voltage: 60 Vdc Minimum Supply Voltage: 20 Vdc Analog Input ranges SAGEON VIGIL INPUT NAME MIN.
  • Page 12: Control Specifications

    SAGEON VIGIL PRODUCT MANUAL EXPANSION (if applicable) will display cell voltages with 0.1% accuracy and a display resolution of 1mV, current transducers within 0.5% and a display resolution of 1A, and temperature sensors within 1/2 F with a display resolution of 0.1 •...
  • Page 13: Alarm Specifications

    SAGEON VIGIL PRODUCT MANUAL 1.3.8 Alarm Specifications The front panel alarm indicators are listed below with their LED indication color, trigger source, and where applicable, the alarm input requirement: FRONT PANEL ALARM INDICATIONS Red LED Major alarm indicator Major Alarm (MAJ) Triggered by FA, VLVA, LVD, HVSD, OC (over-current) or any two or more minor alarms;...
  • Page 14 SAGEON VIGIL PRODUCT MANUAL The front panel alarm indicators are listed below with their LED indication color, trigger source, and where applicable, the alarm input requirement: FRONT PANEL ALARM INDICATIONS Minor Alarm (MIN) Yellow LED Minor alarm indicator Triggered by any single RFA, CEMF, LV, HV, or TA alarm Counter-EMF Cell Alarm Yellow LED CEMF indicator...
  • Page 15: Output Relay Specifications

    SAGEON VIGIL PRODUCT MANUAL 1.3.9 Output Relay Specifications The SAGEON VIGIL provides both Form-C alarm output relays and Form-A control relays for remote monitoring, audible and visual alarm panels, and rectifier control requirements. REMOTE ALARM INDICATIONS Form-C contacts Alarms The SAGEON VIGIL provides screw terminals for 13 form-C alarm relay outputs;...
  • Page 16: Sageon Vigil Installation

    SAGEON VIGIL PRODUCT MANUAL SAGEON VIGIL INSTALLATION 2.1 Introduction 2.2 Selecting a location 2.3 Cabling Requirements 2.4 Installation procedure outline 2.5 Installation guidelines 2.6 Wiring the SAGEON VIGIL INTRODUCTION These instructions provide general information for installing the SAGEON VIGIL in custom applications as a stand alone unit.
  • Page 17: Installation Procedure Outline

    SAGEON VIGIL PRODUCT MANUAL rated jacketed cables and carefully routed to protect the wiring to the SAGEON VIGIL. INSTALLATION PROCEDURE OUTLINE WARNING: The SAGEON VIGIL utilizes connections to battery for power and sensing connections that must include inline protection (fuses or current-limiting resistors) to eliminate potential hazards to personnel and equipment due to accidentally shorted battery connections.
  • Page 18: Installation Guidelines

    SAGEON VIGIL PRODUCT MANUAL Two ground closure true inputs are provided for CEMF Cell alarm inputs (CEMF1 & CEMF2). If a CEMF Cell is included verify it provides the proper input. No inline protection is required for ground closure type inputs. Determine the best cable routing, connection requirements. A ground closure true input is provided for a Low Voltage Disconnect (LVD) alarm.
  • Page 19: Wiring The Sageon Vigil

    SAGEON VIGIL PRODUCT MANUAL The SAGEON VIGIL power inputs are protected against reverse polarity. The analog inputs are polarity sensitive. Reversed connections will not cause any damage but the SAGEON VIGIL will be unable to read the input. This requirement can be confusing. Before starting the general plant wiring, lay any ground jumpers between output relay commons, CTRL RET, and Plant Grounds that are required.
  • Page 20: Binary Inputs

    PLANT GROUND and used with twisted pair cable runs for noise suppression if desired. Note: UNIPOWER CEMF Cells do not typically provide an alarm output. They do provide a fuse alarm that can be connected to the spare fuse (SP) alarm input to provide some measure of direct monitoring if desired.
  • Page 21: Control Relays

    SAGEON VIGIL PRODUCT MANUAL Note: Plant Ground (PGND) and (GRD) must be connected to the grounded terminal of the batteries for the fuse alarms to function properly. See PN drawing for typical connections. The Low Voltage Disconnect alarm input requires a ground closure input. Verify the LVD to be monitored can provide this type of output before proceeding.
  • Page 22: Alarm Output Relays

    SAGEON VIGIL PRODUCT MANUAL Thresholds section after the installation wiring is complete. 2.6.6 Alarm Output Relays The output relays all provide Form C relay contacts supporting normally open or normally closed connections. Two sets of Major and Minor contacts are provided for separate remote monitoring and local annunciation panels.
  • Page 23: Wiring The Cell Monitoring Expansion

    SAGEON VIGIL PRODUCT MANUAL LOWN AMB TEMP, HIGH AMB TEMP, LOW BATT TEMP STR 2, LOW BATT TEMP STR1, HI BATT TEMP STR 2, HI BATT TEMP STR 1 HI LOAD VOLTAGE, HIGH VOLTAGE, LOW VOLTAGE, VERY LOW VOLTAGE, EXT LVD, CEMF 1, CEMF 2. When triggered the Auxiliary alarm will flash the CUR/WD LED on the display panel.
  • Page 24: Communications

    SAGEON VIGIL PRODUCT MANUAL 2.7.2 Communications Use the included telephone style cable (1ft. flat 4 conductor cable with RJ-14 connectors) to connect the corresponding communications port labeled “IOIOI VIGIL” on the CELL MONITORING EXPANSION to the “DIGITAL COMMS” port on the SAGEON VIGIL. Refer to PN 103-3002-XX for more information on the location of the communications ports.
  • Page 25 SAGEON VIGIL PRODUCT MANUAL Current transducers should come preassembled with all appropriate connections to the terminal block provided. The following information is provided for reference only in the event maintenance on the current transducer connections is required. See the PN drawing for available current transducer kits.
  • Page 26 SAGEON VIGIL PRODUCT MANUAL Figure 3. Temperature sensor connector: Red = +5V, Blue = Signal, Black = Return This completes the analog input connections. Stop and verify these connections and update the datasheet if necessary. Go to the Analog Channel Calibration section next to continue with commissioning of the CELL MONITORING EXPANSION.
  • Page 27: Sageon Vigil Operation

    SAGEON VIGIL PRODUCT MANUAL SAGEON VIGIL OPERATION 3.1 Introduction 3.2 Programming the SAGEON VIGIL 3.3 Enabling Thresholds 3.4 Set Thresholds 3.5 Enabling Thresholds 3.6 Analog Calibration 3.7 Set FCCP Scales 3.8 System Options Menu INTRODUCTION 3.1.1 General Description The SAGEON VIGIL was designed to provide all basic meter/alarm functions for monitoring a battery string in an extremely compact, single rack space unit.
  • Page 28: Sageon Vigil Menu Structure

    SAGEON VIGIL PRODUCT MANUAL ambient temperature. When the Load Voltage channel is enabled, the Load Voltage (V ) is also displayed. LED indicators provide visual indications of alarms, HVSD, Equalize status, and power. Test jacks allow for manual verification of analog input voltages (VIGIL inputs only). These test jacks are for reference only and should not be used for gain calibration;...
  • Page 29: Accessing The Menus

    SAGEON VIGIL PRODUCT MANUAL Status: The Status menu only displays the current status of the analog channels. There are no sub-menus for other tasks under this main menu. Alarm: The Alarm menu provides an alarm cut-off control (ACO) of the audible alarm (if audible alarm is enabled) and the specific trigger source of each active alarm.
  • Page 30: Menu Functionality

    SAGEON VIGIL PRODUCT MANUAL The user interface is limited to four push button keys: Escape: This key is used to return to the last menu. Pressing “Escape” from anywhere within the menu structure will abort the current activity and return the user to the next higher level in the menu structure.
  • Page 31 SAGEON VIGIL PRODUCT MANUAL 1. Plant Voltage 2. FCCP 1 current 3. Ambient Temp. 4. Temp. String 1 5. Temp. String 2 6. Load Voltage 7. FCCP Current 2 14. FCCP Current 10 15. PCB Temperature The last value read before entering the Status menu is displayed for each channel. The user can update the displayed channel by pressing the “Select”...
  • Page 32 SAGEON VIGIL PRODUCT MANUAL mode. Pressing “Next” or “Previous” moves the user to the next/last Configure sub- menu, “Escape” moves the user back to the main Configure menu. Enable Thresholds: Lets the user decide which alarm thresholds are active and which are not. The user presses “Select”...
  • Page 33 SAGEON VIGIL PRODUCT MANUAL network communications. The default IP address is 192.168.10.74. The default netmask is 255.255.255.0, and the default gateway address is 192.168.10.1. System Options: Contains several sub-menus for setting system level parameters: Password: Enables or disables a pre-defined sequence of numbers that will prevent access to the Configure and output relay Test menus.
  • Page 34: Programming The Sageon Vigil

    SAGEON VIGIL PRODUCT MANUAL PROGRAMMING THE SAGEON VIGIL This section will deal with the Configure menus only. The Configure menu provides all of the menus necessary to customize the SAGEON VIGIL for the user’s specific requirements. Each sub-menu will be covered in detail which will enable the user to completely configure the SAGEON VIGIL for their specific application.
  • Page 35: Set Thresholds

    SAGEON VIGIL PRODUCT MANUAL Enter the “Enabling Thresholds” menu from the Configure menu by pressing “Select”, then press “Next” until the “Enabling Thresholds” menu appears, then press “Select” again to access the first threshold. The full list of alarm thresholds appears below in the order they would be accessed using the “Next”...
  • Page 36 SAGEON VIGIL PRODUCT MANUAL Alarm Triggering Thresholds 48V PLANT ALARM THRES. FROM DEFAULT HVSD: 50.0 V 60.0 V 57.0 V High Voltage: 50.0 V 60.0 V 56.5 V Low Voltage: 44.0 V 54.0 V 51.5 V Very Low Voltage: 40.0 V 50.0 V 46.5 V High FCCP current:...
  • Page 37: Enabling Channels

    SAGEON VIGIL PRODUCT MANUAL 24V PLANT ALARM THRES. FROM DEFAULT High Voltage Shutdwn: 25.0 V 30.0 V 28.5 V High Voltage: 25.0 V 30.0 V 28.2 V Low Voltage: 22.0 V 27.0 V 25.7 V Very Low Voltage: 20.0 V 25.0 V 23.3 V High FCCP current:...
  • Page 38 SAGEON VIGIL PRODUCT MANUAL Channel Table 1. Plant Voltage FCCP 10 21. RFA 2 31. RFA 12 2. FCCP 1 Load Voltage 22. RFA 3 32. RFA 13 3. FCCP 2 Str 1 Bat Temp 23. RFA 4 33. RFA 14 4.
  • Page 39: Analog Calibration

    SAGEON VIGIL PRODUCT MANUAL BATTERY FUSE* DISABLED SPARE FUSE* DISABLED RECT FAIL 1* ENABLED RECT FAIL 2* ENABLED RECT FAIL 3* ENABLED RECT FAIL 4* ENABLED RECT FAIL 5* ENABLED RECT FAIL 6* ENABLED RECT FAIL 7* ENABLED RECT FAIL 8* ENABLED RECT FAIL 9* ENABLED...
  • Page 40: Calibrate Zero

    SAGEON VIGIL PRODUCT MANUAL 3.6.1 Calibrate Zero The “Calibrate Zero” menu provides a fast and simple means to null out the analog measurement sense leads. This process requires the user to short the measurement leads together as close to the actual measurement point as possible.
  • Page 41: Calibrate Gain

    SAGEON VIGIL PRODUCT MANUAL 5. Press “Select” again and the SAGEON VIGIL will zero the channel and return to the initial display showing the offset as zero: PLANT VOLTAGE READING: 0.00 6. Only those analog channels that were enabled in the Enable Channels menu will appear in sequence.
  • Page 42: Fccp Channel Calibration Calculations

    SAGEON VIGIL PRODUCT MANUAL Calibrate Gain Procedure 1. Enter the “Calibrate Gain” menu from the main Configure menu by Pressing “Select”, then press “Next” until the Calibrate Gain menu appears, then press “Select” again to access the first channel: PLANT VOLTAGE READS: (current value) 2.
  • Page 43: Temperature Calibration Calculations

    3.6.4 Temperature Calibration Calculations The SAGEON VIGIL utilizes UNIPOWER’s standard temperature sensor assemblies that provide a calibrated output of 10 mV per degree Fahrenheit. For SAGEON VIGIL Calibration the easiest method is to measure the sensor output on the temperature inputs at the rear of the SAGEON VIGIL.
  • Page 44: System Options Menu

    SAGEON VIGIL PRODUCT MANUAL SYSTEM OPTIONS MENU The system options menu provides eleven sub-menus that include: 1. Enabling a password for access 2. Setting the voltage display polarity for positive or negative readings 3. Setting the current display polarity for positive or negative readings 4.
  • Page 45: Negative Amps Sub-Menu

    SAGEON VIGIL PRODUCT MANUAL Use the “Next” key to access the next menu. 3.8.3 Negative Amps Sub-Menu The SAGEON VIGIL reads everything as a positive value. In order to display the proper polarity the user must select positive or negative with this menu. Simply set the polarity to match the FCCP 1 polarity using the “Select”...
  • Page 46: System Voltage Sub-Menu

    SAGEON VIGIL PRODUCT MANUAL Note: The audible alarm transducer is rated at 85 DBA @ 10cm which is loud enough for a small office or CEV. Offices where the operator may be more the 25 ft. away or there is a high level of back ground noise should use a separate audible alarm panel operated by an output relay.
  • Page 47: Auxiliary Relay Sub-Menu

    SAGEON VIGIL PRODUCT MANUAL 3.8.9 Auxiliary Relay Sub-Menu The Auxiliary Relay menu allows the user to define the Auxiliary relay as one of the following: an extra Major or Minor alarm output, an Equalize alarm relay, an Audible alarm relay, or any Alarm Condition output.
  • Page 48: Sageon Vigil Test & Verification

    SAGEON VIGIL PRODUCT MANUAL SAGEON VIGIL TEST & VERIFICATION 4.1 Introduction 4.2 Test Analog Channels 4.3 Test Binary Channels 4.4 Test Output Relays 4.5 Test LED’s 4.6 Test LCD 4.7 Test Audible Alert INTRODUCTION The SAGEON VIGIL Test menu provides for comprehensive testing of all input and output functions. Analog and Binary channels can be continuously monitored to verify operation or troubleshoot the power plant.
  • Page 49: Test Binary Channels

    SAGEON VIGIL PRODUCT MANUAL TEST BINARY CHANNELS Press “Select” when the Binary Channels menu appears to enter the binary test mode. The first enabled binary channel will appear with its current status displayed and updated continuously. The user can press “Next”...
  • Page 50: Led Test Mode

    SAGEON VIGIL PRODUCT MANUAL other test modes. Press “Escape” to return to the main menus or the idle display screen. LED TEST MODE Press “Select” when the display reads LAMP OFF to activate all front panel LED’s at once. All LED’s should be illuminated.
  • Page 51: Maintenance

    SAGEON VIGIL PRODUCT MANUAL MAINTENANCE The SAGEON VIGIL should not require any regular maintenance. Once a year, the analog channel calibration should be verified against actual measurements. On a 2 to 5 year basis, a complete system test should take place that checks all alarm and output functions to make sure alarm detection, control functions, and output relays work properly.
  • Page 52: Network, Webpage, And Snmp

    SAGEON VIGIL PRODUCT MANUAL NETWORK, WEBPAGE, AND SNMP The SAGEON VIGIL can be monitored remotely via the integral webserver and SNMPv1 agent. Network settings are configured locally via the VIGIL keypad or via the webpage interface. The default IP address is 192.168.10.74. WEBPAGE Battery voltage, FCCP float current channels, temperature channels, and present alarm status can all be monitored remotely using the webpage.
  • Page 53: Sparing / Accessories, Optional Parts

    SAGEON VIGIL PRODUCT MANUAL SPARING / ACCESSORIES, OPTIONAL PARTS SAGEON VIGIL parts can be shipped overnight from the factory for critical replacements if necessary. The following list of internal parts can be used to order spares or replacements: Part Description Part Numbers Where Used Main Processor Board...
  • Page 54 SAGEON VIGIL PRODUCT MANUAL lengths available; contact factory. Inline fuse, 0.5A Kit 385-2778-11 Protection of VIGIL wiring Inline fuse, 2.0A Kit 385-2778-13 Protection of VIGIL wiring Inline fuse, 3.0A Kit 385-2778-14 Protection of VIGIL wiring Inline Resistor Kit 385-2789-00 Protection of shunt wire connections Current transducer, 200A, open 385-5973-200...
  • Page 55: Appendix Listings

    SAGEON VIGIL PRODUCT MANUAL APPENDIX LISTINGS 8.1 FLOW CHARTS FOR SAGEON VIGIL MENU STRUCTURES • Appendix A: Main Menus • Appendix B: Configuration Menu • Appendix C: Enable Channels Menu • Appendix D: Enable Thresholds Menu • Appendix E: Set Thresholds Menu •...
  • Page 56 SAGEON VIGIL PRODUCT MANUAL Appendix A: Main Menus The top level menus of the VIGIL: This menu will only appear if enabled. Additional cell monitoring channels will also appear if a monitoring expansion is connected. Idle Menus Select Mode Description Idle screen w/o load voltage...
  • Page 57 SAGEON VIGIL PRODUCT MANUAL Appendix B: Configuration Menu Top level of the CONFIGURE set of menus. Menu Submenu Description MANUAL EQ CONFIGURE Selecting this menu allows setting the number of hours for a manual equalize. TIME* SYSTEM Submenus allow enabling system password, backlight on/off, aux relay OPTIONS mapping, choosing equalization/sleep modes.
  • Page 58 SAGEON VIGIL PRODUCT MANUAL Appendix C: Enable Channels Menu Configure Menu Submenu Description ENABLE FCCP 2 Enables or disables FCCP 2 input. CHANNELS FCCP 3 Enables or disables FCCP 3 input. FCCP 4 Enables or disables FCCP 4 input. FCCP 5 Enables or disables FCCP 5 input.
  • Page 59 SAGEON VIGIL PRODUCT MANUAL Appendix D: Enable Thresholds Menu Configure Menu Submenu Description ENABLE HVSD VOLTAGE Enables/disables the high voltage shutdown threshold. THRESH. STR 1 TEMP DIFF Enables/disables the battery string 1 temperature Difference threshold STR 2 TEMP DIFF Enables/disables the battery string 2 temperature Difference threshold LOW AMB TEMP Enables/disables the low ambient temperature threshold.
  • Page 60 SAGEON VIGIL PRODUCT MANUAL Appendix E: Set Thresholds Menu Configure Menu Submenu Description HVSD VOLTAGE Changes the High Voltage shutdown alarm threshold. THRESHOLDS STR 1 TEMP DIFF Changes the battery string 1 temperature difference alarm threshold. STR 2 TEMP DIFF Changes the battery string 2 temperature difference alarm threshold.
  • Page 61 SAGEON VIGIL PRODUCT MANUAL Appendix F: Calibrate Zero Menu Configure Menu Submenu Description CALIBRATE PLANT VOLTAGE Remove offset from the "PLANT VOLTAGE" analog input. ZEROS FCCP CURRENT 1 Remove offset from the FCCP 1 analog input. AMBIENT TEMP Remove offset from the "AMBIENT TEMP " analog input. TEMP STRING 1 Remove offset from the "TEMP STRING 1"...
  • Page 62 SAGEON VIGIL PRODUCT MANUAL Appendix H: Set FCCP Scales Menu Configure Menu Submenu Description SET FCCP FCCP 1 SCALE Allows changing the maximum current rating of the FCCP 1. SCALES FCCP 2 SCALE Allows changing the maximum current rating of the FCCP 2. FCCP 3 SCALE Allows changing the maximum current rating of the FCCP 3.
  • Page 63 SAGEON VIGIL PRODUCT MANUAL Appendix J: Auxiliary Relay Menu System Options Submenu Description Menu AUX RELAY AUX. RELAY FUNCT Displays whether or not the auxilliary relay function is enabled or MENU IS: x disabled. Leads to a set of menus for using the auxiliary relay be triggered by any of ALRM CND x a number of different alarm conditions.
  • Page 64 SAGEON VIGIL PRODUCT MANUAL The auxiliary relay maps to the FCCP current 10 alarm. FCCP CURRENT 10 The auxiliary relay maps to any over current alarm. ANY OVER CURRENT HIGH VOLTAGE The auxiliary relay maps to the high voltage alarm. LOW VOLTAGE The auxiliary relay maps to the low voltage alarm.
  • Page 65 SAGEON VIGIL PRODUCT MANUAL Test Menu Submenu Description Output Relays MAJOR x Indicates if the MAJOR alarm relay is energized. HVSD x Indicates if the HVSD alarm relay is energized. RS x Indicates if the RS alarm relay is energized. EQ x Indicates if the EQ alarm relay is energized.
  • Page 66 PROPRIETARY INFORMATION NOT TO BE COPIED, USED, TRANSMITTED, OR DISCLOSED WITHOUT PRIOR WRITTEN PERMISSION FROM UNIPOWER, LLC.
  • Page 75 PROPRIETARY INFORMATION NOT TO BE COPIED, USED, TRANSMITTED, OR DISCLOSED WITHOUT PRIOR WRITTEN PERMISSION FROM UNIPOWER, LLC.
  • Page 76 WIRE MARKER LABELS PSMC CURRENT CURRENT TRANS.1 TRANS.2 PROPRIETARY INFORMATION NOT TO BE COPIED, USED, TRANSMITTED, OR DISCLOSED WITHOUT PRIOR WRITTEN PERMISSION FROM UNIPOWER, LLC.