Connection Notes - Siemens SITRANS LPS200 Operating Instructions Manual

Rotating paddle switch
Hide thumbs Also See for SITRANS LPS200:
Table of Contents

Advertisement

Available languages

Available languages

Connection Notes

Before opening the lid, ensure there are no dust deposits around the SITRANS LPS200.
Ensure that the atmosphere around SITRANS LPS200 is settled.
Use a fuse for the signal output and power supply (max. 10 A, fast or slow, HBC,
250V).
Make sure the main voltage does not exceed the maximum voltage listed on the
product label and the setting of the voltage selector.
In case of inexpert handling or handling malpractice, the electric safety of the
device cannot be guaranteed.
Provide protection for relay contacts to protect the device against spikes if inductive
loads are connected.
Switching Logic (universal voltage, DPDT)
A5E34210883
SITRANS LPS200 – OPERATING INSTRUCTIONS
FSL
SPDT
7 6 5
DPDT
8 9 10
PNP
1 2 3
yellow
SPDT
7
6
DPDT
8
9
PNP
1
2
green
Power
failure
7
6
5
8
9
FSH
FSH:
Use this setting when sensor
is used as a full detector.
7 6 5
Power failure or line break is
regarded as "full" signal (pro-
tection against overfilling).
8 9 10
FSL:
Use this setting when sensor
is used as an empty detector.
1 2 3
Power failure or line break is
regarded as "full" signal (pro-
green
tection against overfilling).
Factory setting: FSL
5
7
6
5
10
8
9
10
3
1
2
3
yellow
10
1
2
3
Page EN-13