4

Planning

Compatibility

4 Planning
4.1 Compatibility

4.2 Fields of application

4.3 Installation site

4.4 Environmental influences

22
Building Technologies
Fire Safety
Compatible with control panels that support the FDnet/C-NET detector line.
Detector line
FC20xx
FDnet
C-NET
X = compatible
– = not compatible
You will find details in the 'List of compatibility'.
The manual call points are intended for use in places where a fire can be detected
by people who can manually trigger an alarm.
The manual call points must be installed in easily accessible places at a height of
0.9...1.6 m on an even surface.
Observe the country-specific regulations for the exact installation height!
If the devices are used in industrial applications, consultation with the project
manager is required, since plastics do not withstand certain environmental
conditions.
The following factors must be taken into consideration:
Chemicals
Temperature
Moisture
Control panel
FC72x
X
-
X
SIGMASYS
AlgoRex
A6V10374021_c_en_--
2014-07-01