7.1.5.3 The control of preventing the over current of the compressor:

During the starting process of the compressor, if the current of the compressor is greater than 15.5A
/17A(18K/24K)for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such
state appears 3 times in 20 minutes, stop the compressor and alarm, and confirm the malfunction.
Then continue to run it only after the power is off.
During the starting process of the compressor, if the AC current is greater than 14.5A/15A(18K/24K),
the frequency of the compressor decreases at the speed of 1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13.5A/14A(18K/24K),
the frequency of the compressor decreases at the speed of 0.1HZ/second.
During the starting process of the compressor, if the AC current is greater than 13A/13A(18K/24K),
the frequency of the compressor increases at the prohibited speed.
During the starting process of the compressor, if the AC current is greater than 11.5A/12A(18K/24K)
the frequency of the compressor increases at the speed of no faster than 0.1HZ/second.

7.1.5.4 The protection function of AC current:

During the starting process of the compressor, if the AC current is greater than 15.5A/17.5A(18K/24K)
for 3 seconds, stop the compressor and alarm, after 3 minutes, start it again, if such state appears 3
times in 20 minutes, stop the compressor and alarm, and confirm the malfunction. Then continue to
run it only after the the power is off.
During the starting process of the compressor, if the AC current is greater than 14.5A 15A(18K/24K),
the frequency of the compressor decreases at the speed of 1HZ/second.
The compressor stops
N Decreasing the frequency rapidly
P Decreasing the frequency slowly
Q Prohibiting increasing the frequency
R Increasing slowly
19
Functions and control
(18K/24K)
Fgh_t1 63 /63
Fgh_t2 59 /59
Fgh_t3 56 /57
Fgh_t4 53 /51
Fgh_t5 40 /40