NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Outdoor unit
Model
precharged
MUZ-GL18NA
3 lb. 9 oz.
MUZ-GL18NAH
MUY-GL18NA
NOTE: Refrigerant piping exceeding 33 ft. requires additional refrigerant charge according to the calculation.
Outdoor unit
Model
precharged
MUZ-GL24NA
4 lb. 3 oz.
MUZ-GL24NAH
MUY-GL24NA
OBH733D
Refrigerant piping length (one way): ft.
25
30
40
0
1.08
3.24
Calculation: X oz. = 1.08/5 oz./ft. × (Refrigerant piping length (ft.) - 25)
Refrigerant piping length (one way): ft.
33
40
50
0
4.14
10.06
Calculation: X oz. = 2.96/5 oz./ft. × (Refrigerant piping length (ft.) - 33)
24
50
60
70
5.40
7.56
9.72
60
70
15.98
21.90
80
90
100
11.88
14.04
16.20
80
90
100
27.82
33.74
39.66