Outdoor Unit Failure Recall Mode Table - Mitsubishi Electric MUZ-GL09NA-U1 Service Manual

Split-type air conditioners unit outdoor unit
Hide thumbs Also See for MUZ-GL09NA-U1:
Table of Contents

Advertisement

3. Outdoor unit failure recall mode table

The upper
lamp of the
OPERATION
Abnormal point
INDICATOR
(Failure mode/protection)
lamp
(Indoor unit)
OFF
None (Normal)
1-time fl ash
Indoor/outdoor
2.5 seconds
communication, receiving
OFF
error
Indoor/outdoor
communication, receiving
error
2-time fl ash
Outdoor power system
2.5 seconds
OFF
3-time fl ash
Discharge temperature
2.5 seconds
thermistor
OFF
Defrost thermistor
Fin temperature thermistor
P.C. board temperature
thermistor
Ambient temperature
thermistor
Outdoor heat exchanger
temperature thermistor
4-time fl ash
Overcurrent
2.5 seconds
OFF
Compressor synchronous
abnormality (Compressor
start-up failure protection)
5-time fl ash
Discharge temperature
2.5 seconds
OFF
6-time fl ash
High pressure
2.5 seconds
OFF
7-time fl ash
Fin temperature/ P.C. board
2.5 seconds
temperature
OFF
8-time fl ash
Outdoor fan motor
2.5 seconds
OFF
9-time fl ash
Non-volatile memory data
2.5 seconds
OFF
Power module (IC700)
(MUZ-GL09/12/15/18, MUY-
GL09/12/15/18)
IGBT module (IC700)
(MUZ-GL24, MUY-GL24)
OBH733D
LED indication
(Outdoor P.C. board)
Any signals from the inverter P.C.
board cannot be received normally for
3 minutes.
Although the inverter P.C. board
sends signal "0", signal "1" has been
received 30 consecutive times.
Overcurrent protection cut-out
operates 3 consecutive times within
1 minute after the compressor gets
started.
1-time fl ash every
Thermistor shorts or opens during
2.5 seconds
compressor running.
3-time fl ash
2.5 seconds OFF
4-time fl ash
2.5 seconds OFF
2-time fl ash
2.5 seconds OFF
11-time fl ash
Large current fl ows into the power
2.5 seconds OFF
module (IC700) (MUZ-GL09/12/15/18,
MUY-GL09/12/15/18)/ IGBT module
(IC700) (MUZ-GL24, MUY-GL24).
12-time fl ash
Waveform of compressor current is
2.5 seconds OFF
distorted.
Temperature of discharge temperature
thermistor exceeds 241°F (116°C),
compressor stops.
Compressor can restart if discharge
temperature thermistor reads
212°F (100°C) or less 3 minutes later.
Temperature indoor coil thermistor
exceeds 158°F (70°C) in HEAT
mode. Temperature defrost thermistor
exceeds 158°F (70°C) in COOL mode.
7-time fl ash
Temperature of the fi n temperature
2.5 seconds OFF
thermistor on the inverter P.C. board
exceeds 167 - 187°F (75 - 86°C) (MUZ-
GL09/12/15/18, MUY-GL09/12/15/18)/167
- 176°F (75 - 80°C) (MUZ-GL24, MUY-
GL24), or temperature of P.C. board
temperature thermistor on the inverter
P.C. board exceeds 162 - 185°F (72
- 85°C) (MUZ-GL09/12/15/18, MUY-
GL09/12/15/18)/158 - 167°F (70 - 75°C)
(MUZ-GL24, MUY-GL24).
Outdoor fan has stopped 3 times in a
row within 30 seconds after outdoor
fan start-up.
5-time fl ash
Non-volatile memory data cannot be
2.5 seconds OFF
read properly.
6-time fl ash
The interface short circuit occurs
2.5 seconds OFF
in the output of the power module
(IC700) (MUZ-GL09/12/15/18, MUY-
GL09/12/15/18)/IGBT module (IC700)
(MUZ-GL24, MUY-GL24).
The compressor winding shorts circuit.
44
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (10-3.).
Condition
•Refer to 10-5.
to check miswiring and
serial signal error.
•Refer to 10-5.
to check miswiring and
serial signal error.
• Reconnect
connectors.
• Refer to 10-5.
to check inverter/
compressor".
• Check stop valve.
• Refer to 10-5.
"Check of outdoor
thermistors".
Defective outdoor
thermistors can be
identifi ed by checking
the blinking pattern of
LED.
• Reconnect
compressor connector.
• Refer to 10-5. "How
to check inverter/
compressor".
• Check stop valve.
• Reconnect
compressor connector.
• Refer to 10-5. "How
to check inverter/
compressor".
• Check refrigerant
circuit and refrigerant
amount.
• Refer to 10-5. "Check
of LEV".
• Check refrigerant
circuit and refrigerant
amount.
• Check stop valve.
• Check around outdoor
unit.
• Check outdoor unit air
passage.
• Refer to 10-5. "Check
of outdoor fan motor".
• Refer to 10-5. "Check
of outdoor fan motor".
Refer to 10-5. "Check
of inverter P.C. board".
• Replace the inverter
P.C. board.
• Refer to 10-5.
to check inverter/
compressor".
Indoor/outdoor
unit failure
Remedy
mode recall
recall function
function
How
How
"How
"How
Outdoor unit
failure mode

Hide quick links:

Advertisement

Table of Contents
loading