www.haiwell.com
Ethernet +:
Support the standard Modbus TCP protocol, it can communicate with the configuration, touch screen, PLC and
other third-party host computers, which must support Modbus TCP protocol. Among them:
Ethernet default parameters:
IP: 192.168.1.111
Subnet mask: 255.255.255.0
Gateway: 192.168.1.1

2.4. Module parameter configuration method introduction, when the module is used as remote IO

There are three ways to configure remote IO parameters:
It can be configured via programming software - tools - remote modules (recommended);
1
It can be configured via the hardware configuration and TO instructions, when the module is hung behind the host PLC
2
through the parallel port;
It can be configured via MODW instructions through the serial communication.
3

2.5. Parameter configuration example: The module is configured by programming software remote module tool

Hardware connection

Through the RS485 communication port (the terminals of A +,B- on the module) connection: If the computer has a serial
1
port, you can use the converter of 232 to 485 connecting with the module; if it has one USB interface, you can use the
converter of USB to 485 connecting with the module.
Through the connection of Ethernet + communication interface: You can connect the module with the computer's
2
network port directly by the standard network cable, or take the computer and module connected to the switch.

Software operation steps

Click on the the menu bar tool of programming software- "remote module":
Click the button
in the pop-up window to open the "Online" window. The module default address is 1,19200, N 8 2 RTU,
the online success is as follows: