Zeta Alarm Systems Prem1er Quatro Installation Manual

Zeta Alarm Systems Prem1er Quatro Installation Manual

Mkii protocol - one to four loops analogue addressable fire alarm panel
Table of Contents

Advertisement

Quick Links

PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII)
MKII PROTOCOL - ONE TO FOUR LOOPS ANALOGUE
ADDRESSABLE FIRE ALARM PANEL
INSTALLATION MANUAL
Doc No: GLT-215-7-1
www.acornfiresecurity.com
www.zetaalarmsystems.com
www.acornfiresecurity.com
Firmware Versions PANEL 1.84 & LOOP 3.70
Issue: 1.36

Advertisement

Table of Contents
loading

Summary of Contents for Zeta Alarm Systems Prem1er Quatro

  • Page 1 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions PANEL 1.84 & LOOP 3.70 MKII PROTOCOL - ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL INSTALLATION MANUAL Doc No: GLT-215-7-1 www.zetaalarmsystems.com Issue: 1.36 www.acornfiresecurity.com...
  • Page 2: Table Of Contents

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 Manual Sections 1- SAFETY INFORMATION..........................4 1.1 INSTALLATION INFORMATION......................4 1.2 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL............4 1.3 BATTERY INFORMATION........................4 1.4 PRODUCT DISPOSAL AT THE END OF IT’S WORKING LIFE..............4 1.5 USING THIS MANUAL...........................4 1.6 FIRE ALARM SYSTEMS CODE OF PRACTICE..................5 1.7 EQUIPMENT WARRANTY........................5...
  • Page 3 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 5.1 LOCATING THE FIRE ALARM CONTROL PANEL................18 5.2 FIXING THE BACK BOX TO THE WALL....................18 5.3 MAINS WIRING RECOMMENDATIONS..................19 5.4 PLANNING CABLE ENTRY.......................19 5.5 CONNECTING THE MAINS POWER....................19 5.6 CONNECTING THE BATTERY......................20 6- INSTALLING THE DEVICES..........................21 6.1 ADDRESSABLE LOOP WIRING......................21...
  • Page 4 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 8.2 RING NETWORK..........................35 8.3 BUS NETWORK..........................35 8.4 CONFIGURING THE NETWORK......................36 8.5 MODBUS............................37 8.6 REPEATER PANEL...........................38 9- PROGRAMMING............................39 9.1 CAUSE AND EFFECT........................39 9.1.1 ACTIONS........................39 9.1.2 LOGIC..........................40 9.1.3 CLASS CHANGE......................41 9.1.4 DISABLE RELAYS......................41 9.1.5 DISABLE OUTPUTS......................41 9.1.6 DAY &...
  • Page 5: 1- Safety Information

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 1- SAFETY INFORMATION WARNING: Read this section completely before commencing installation. 1.1 INSTALLATION INFORMATION THIS FIRE ALARM CONTROL PANEL IS CLASS 1 EQUIPMENT AND MUST BE EARTHED. This equipment must be installed and maintained by a qualified and technically experienced person.
  • Page 6: Fire Alarm Systems Code Of Practice

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 1.6 FIRE ALARM SYSTEMS CODE OF PRACTICE This manual is not designed to teach Fire Alarm System design. It is assumed that the System has been designed by a competent person, and that the installer has an understanding of Fire Alarm System components and their use.
  • Page 7: Explanation Of Access Levels

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 2.2 EXPLANATION OF ACCESS LEVELS The Premier Quatro System has the following access levels. ACCESS LEVEL ACCESSED BY ACCESS METHOD FUNCTIONS ACCESSED View Panel General public Default state Override delay (if used) Start/stop sounders...
  • Page 8: Panel Specification - Electrical

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 2.4 PANEL SPECIFICATIONS - ELECTRICAL ELECTRICAL DESCRIPTION VALUE MAINS VOLTAGE 230 V AC + 10% / - 15% BATTERY VOLTAGE 2 x 12V SLA (27.6V DC @ 20 C) (7Ah – 17Ah) POWER SUPPLY NON-INTEGRAL (SWITCH MODE) DC OUTPUT: Vmax = 31V ,Vmin = 19V...
  • Page 9: Fuse Specifications - Power Supply Controller Pcb

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 2.5 FUSE SPECIFICATIONS - Power Supply Controller PCB Fuse Label Rating Description A_Fuse 2.5A PSU Output – Channel A B_Fuse 2.5A PSU Output – Channel B Link Fuse Battery fuse Doc No: GLT-215-7-1...
  • Page 10: Fuse Specifications - Cie Termination Pcb

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 2.6 FUSE SPECIFICATIONS - CIE Termination PCB Fuse Rating Description NOT USED NOT USED F 500 mA 24V Aux Supply Fuse NOT USED NOT USED F 500 mA Conventional Sounder Circuit SND 1 F 500 mA Conventional Sounder Circuit SND 2...
  • Page 11: 3- Introduction To The Quatro Panel

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 3- INTRODUCTION TO THE QUATRO PANEL 3.1 ABOUT THE PREMIER QUATRO FIRE ALARM PANEL  The Premier Quatro is a 1 to 4 loop Analogue addressable control panel that uses the Zeta Fyreye MKII Protocol. ...
  • Page 12: Navigating The Panel Menus

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 3.3 NAVIGATING THE PANEL MENUS The Quatro panel has 2 menus, user and installer. Entering the user code (Default 1111) accesses the user menu and entering the Installer password (Default 2222) accesses the Installer menu.
  • Page 13: Indicating Different Panel States

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 3.5 INDICATING DIFFERENT PANEL STATES During Normal operation the panel will be in one of the following states depending on the status of the devices connected to the panel, and user intervention.
  • Page 14: The Fault Condition

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 3.5.3 The Fault Condition All faults are indicated by a flashing yellow common fault LED, and either an additional fault LED, or an LCD message. Faults can be divided into 2 types, “Faults” and “Device Faults”. Device Faults are any fault associated with a particular address on the loop.
  • Page 15: 4- Designing The System

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 4 - DESIGNING THE SYSTEM 4.1 DESIGNING THE SYSTEM The first consideration when designing the fire alarm system is the type or category of fire protection that is required for the building.
  • Page 16: Maximum Loop Cable Length Recommendations

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 4.4 MAXIMUM LOOP CABLE LENGTH RECOMMENDATIONS With an addressable system, some care must be taken when calculating the appropriate cable gauge for the system. The main limitation is that during an alarm condition (maximum current draw), the voltage at all detectors must be at least 17 Volts with at least 5V of superimposed data signal.
  • Page 17: Addressable Sounder Circuit Controller

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 4.6.5 PCB CONVENTIONAL SOUNDER CIRCUITS The termination PCB has 2 conventional sounder circuit outputs, with a maximum capacity of 450 mA each. Please note that conventional sounders should be wired as shown in the diagram below: *The descriptions of sounders in this section also apply to flashers and combined sounder / flashers.
  • Page 18: Pre Commissioning Checks List

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 4.7 SYSTEM SPARE CAPACITY The UK Fire alarm system code of Practice for Designing, Installing, Commissioning & maintaining fire alarm systems, BS5839 recommends allowing at least 25% free capacity when designing a fire system. This is a good precaution as it allows for:- ...
  • Page 19: 5- Mounting The Fire Alarm Control Panel

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 5 MOUNTING THE FIRE ALARM CONTROL PANEL The Premier Quatro comes with many cable entry holes. If another entry hole is required, it is strongly recommended that the panel door is removed to avoid accidental damage.
  • Page 20: Mains Wiring Recommendations

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 5.3 MAINS WIRING RECOMMENDATIONS The Mains supply to the FACP is fixed wiring, using Fire resisting 3-core cable (Between 1 mm² and 2.5mm²), fed from an isolating double pole switch fused spur, and fused at 3A.
  • Page 21: Connecting The Battery

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 The AC Live (L), Earth (E) and Neutral (N) connections are marked on the power supply cage (top right of Figure 3). It is essential that the mains Earth cable is connected to the PSU’s Earth terminal. The incoming mains cable should be kept separate from the loop cables to help minimize mains interference.
  • Page 22: 6- Installing The Devices

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6 - INSTALLING THE DEVICES 6.1 ADDRESSABLE LOOP WIRING The Premier Quatro can be fitted with 1 or 4 addressable loop cards. One addressable loop can be connected to each loop card. Addressable detectors, addressable call points, addressable loop powered sounders and several other interface units can be fitted to these loops.
  • Page 23: Specific Device Wiring Instructions

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6.3 SPECIFIC DEVICE WIRING INSTRUCTIONS 6.3.1 CP3/AD Manual Call Point Led Indicator: OFF = Quiescent YELLOW = Isolating RED = Fire The CP3/AD call point has a built in isolator which can be wired in circuit or not used. This is done by means of not wiring to the negative out terminal on the call point.
  • Page 24: Zai-Mi Input Module

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 The connection for the detectors bases is made as follows: Terminal L1IN is –ve (Blue) Terminal L2 is +ve (Brown) These are the only two connections required. Deep Base MKII-CB/D Common Base MKII-CB 6.3.3 ZAI - MI Input Module...
  • Page 25: Zasc-Mi Sounder Control Module

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6.3.5 ZASC – MI Sounder Control Module The ZASC requires an external 24vdc power supply (as shown in the above diagram). The EOL for the sounder circuit is 10KΩ. When using the ZASC make sure the PSU being used has a fault output relay, so that in the event of a power supply fault it is reported to the control panel.
  • Page 26: Xtratone Sounder/Sounder Flasher

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6.3.7 Xtratone Sounder/Sounder Flasher The Xtratone sounder or sounder flasher is a wall mount sounder. The programming of the sounder is done via the DIP switch mounted on the inside (front).
  • Page 27: Remote Led Indicator

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6.3.9 Remote LED Indicator Ceiling Mount (MKII-ARL/C) Wall Mount (MKII-ARL/W) There are two versions of the remote LED, Wall mounted and Ceiling mounted. The ceiling mounted version requires a standard detector base.
  • Page 28: Setting The Device Address (Detectors, Call Points, Sounders And Interface Units)

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6.4 SETTING THE DEVICE ADDRESS (DETECTORS, CALL POINTS, SOUNDERS & INTERFACE UNITS) 6.4.1 SOFT AND HARD PROGRAMMING The MKII Handheld Programmer is designed to complement all MKII devices and to assist the commissioning engineer on site. The unit will softly address all devices without using the incorporated dip-switch on the field devices.
  • Page 29 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 OFF OFF OFF OFF ON ON ON 58 OFF ON OFF OFF OFF ON ON 101 OFF ON OFF ON OFF OFF ON OFF ON ON ON 59 OFF OFF ON OFF OFF OFF ON ON 102...
  • Page 30: Fire Relay (Voltage Free Charge Over Contacts)

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 OFF ON OFF ON ON OFF 188 OFF OFF OFF OFF ON OFF 231 OFF OFF OFF ON OFF OFF OFF OFF ON OFF ON ON OFF 189 OFF ON OFF OFF OFF OFF ON OFF 232...
  • Page 31: Fault Relay (Voltage Free Changeover Contacts)

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 6.6 FAULT RELAY (VOLTAGE FREE CHANGEOVER CONTACTS) The fault relay (R. FAULT) is energised in the quiescent condition. When any type of fault occurs, this is indicated by the fault relay to ensure fail safe operation, even in the event of total power loss.
  • Page 32: Power Supply

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 7.1.2 POWER SUPPLY Quatro is normally supplied with an external PSU Charger card. This is the approved PSU CHARGER option. It can also operate with a power supply which is part of the panel’s MOTHERBOARD PCB. This is the MOTHERBOARD CHARGER Option. To ensure that the correct fault monitoring is selected, the installer must indicate whether the MOTHERBOARD CHARGER or the PSU CHARGER is being used, as follows: ...
  • Page 33: Led Flash Setup

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 (b) Level 2 or Installer Password (Default 2222) Only one level 2 password is permitted by the panel at any time. It is essential that the level 2 password is kept secret from the panel users (and of course the general public).
  • Page 34: Alarm Tone Setup

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 CONNECTION TO NETWORK CARD RS232 PAPER FEED CONNECTION TO 24v DC FRONT LOADING COVER 7.1.11 ALARM TONE SETUP In the Fyreye MKII Protocol, the Quatro allows the alarm tone to be chosen from a list of 16 predefined tones (The panel will be set at a default of TONE 0).
  • Page 35: Zone Labels

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 7.1.14 ZONE LABELS The subdivision of a fire alarm system was explained in Section 3, the Premier Quatro panel being capable of assigning 20 zones. When a fire is enunciated, the zone number in which the fire is located is indicated on the alphanumeric display. In addition to its numerical description, a zone can be identified by a text label, e.g.
  • Page 36: Viewing Device Status

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 7.1.17 VIEWING DEVICE STATUS To view the status of any loop device (point):  Turn the key switch clockwise to the Controls Enabled Position. The controls Active LED will light. ...
  • Page 37: Configuring The Network

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 8.4 CONFIGURING THE NETWORK There are 3 types of network card available for the Premier Quatro Panel. OLD STANDARD NETWORK CARD NEW MODBUS NETWORK CARD GATEWAY NETWORK CARD The Gateway Network Card The Standard Network has an RS485 repeater...
  • Page 38: Modbus

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 View Current Topology Shows the last configured network topology (Will show which of the three configurations the panel was last networked it, as described above). Shared Zones These settings can be configured to allow the panel Zone LEDs to be shared across the network.
  • Page 39: Repeater Panel

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 Network status registers These registers will contain the status of the network of Quatro addressable panels.  Node configuration  Network status  Network topology Zone status registers These registers contain the zones status.
  • Page 40: 9- Programming

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 9- PROGRAMMING 9.1 CAUSE AND EFFECT 9.1.1 ACTIONS The Premier Quatro system has very comprehensive Cause and Effect capabilities (known in the panel menu as Actions). The Default factory configuration is that any alarm will activate all outputs on the panel.
  • Page 41: Logic

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 ACTION MODIFICATION <0005>:001 DLY:010 Modify Action Number 5. Total Actions 10. I Panel Gen Alarm Input: Panel – General Alarm. O Zone RANGE 001 To 003 Outputs ON* Output: Zone –...
  • Page 42: Class Change

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 9.1.3 CLASS CHANGE If it is required to configure an I/O to act as a class change input then it can be enabled by:  Enter the Actions menu via the Installer menu (2222 password). ...
  • Page 43: Configuration Software

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 FIRST ALARM: Z001 – FIRST FLOOR The [END DELAY] label is erased from the display when either the longest sounder LAST ALARM : Z003 – THIRD FLOOR delay has expired or the sounder delay has been overridden by pressing F4.
  • Page 44 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 Logic Events Screen The logic events can be created the same way by simply clicking on the inputs and then dragging it to the required output. Same with cause and affects you have the ability to change event type, action settings, add delays and...
  • Page 45: 10- Menu Command Structure

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 10- MENU COMMAND STRUCTURE This section summarises the complete command structure of the Quatro panel. Various functions can be accessed at different levels within the panel, the NO ACCESS level, the CONTROLS ACTIVE level, the USER level, and the INSTALLER level. At the NO ACCESS level (where the black controls key is switched OFF), the basic status of the panel is indicated by its LEDs and alphanumeric display (LCD).
  • Page 46: Installer Level (Level 2)

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 10.2 INSTALLER LEVEL (LEVEL 2) Default Password 2222 PRIMARY SELECTION SECONDARY SELECTION TERTIARY SELECTION OR COMMENT Loop Autosearch Searches for all devices on specified loop & displays: VALID: xxx DOUBLE ADDRESS: xxx MODIFIED TYPE: xxx...
  • Page 47: Cause & Effect Table

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 Check version Panel s/w version & s/w versions of each loop card SW Upgrade Enables an authorised engineer to upgrade the Quatro software, using PC software Enable USB Config From F/W V 1.77 onwards, the panel must be put into USB access Mode before the panel will communicate with the PC software.
  • Page 48: 11- Disablements

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 Panel RMT/No/Yes (1-032) Delay Outputs ON Alarm + Flash (000–999) Outputs OFF Alert + Flash Sounders ON* Emergency + Flash Sounders OFF Flasher Relays ON Alarm Relays OFF Alert PCB Sounder One ON...
  • Page 49: Device Disablement

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 the control buttons F1 and F2 which correspond to [ - ], the previous disabled zone, and [ + ], the next disabled zone. Alternatively, up to 10 disabled zones (without text labels) can be displayed in one screen as follows. Select any key followed by Level 1 password (default 1111), and then Zones followed by Show Disabled Zone.
  • Page 50: Relay Disablement

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 11.5 RELAY DISABLEMENT Relay outputs can also be disabled. These can either be addressable output units on any of the loops or a PCB output relay (ALARM or FAULT).
  • Page 51: 13- Fault Finding

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 [ - ] [ + ] [NEXT pressing the control buttons F1 and F2 which correspond to [ - ], the previous disabled zone, and [ + ], the next disabled zone. NOTE that if a fault condition or more than one of the disablement or test conditions described in sections 13 and 14 are present, then the condition displayed on the main screen is dependent on the following order of priority: ...
  • Page 52: False Alarms

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 FAULT 0015/0021 30/06/09 09:41 MKII-AHR (1.4.24) W TYPE A device has been changed for one of a different type. TEXT : Store Room FAULT 0004/0021 30/06/09 16:59 A device in that zone is communicating a fault condition to the panel with its analogue ZAZM-M...
  • Page 53: Earth Faults

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 run the panel on batteries only for half an hour or so to try to discharge the batteries. If this doesn’t solve the problem, replacement batteries will be required. 13.5 EARTH FAULTS An EARTH fault indicates that something is shorting to earth (usually through the cable screen).
  • Page 54 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 Faults Log (1024): FAULT <0123>/0512 01/07/15 12:34 The screen will show the event number, the total no. of faults, the date, the Ter-STD (1.002) REMOVED time, the type of fault that has occurred, the address of the device in fault, which TEXT : Room 12C loop that it is in, and its location (i.e.
  • Page 55: 15- Standby Battery Requirements

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 15- STANDBY BATTERY REQUIREMENTS 15.1 PANEL & DEVICE CURRENT RATINGS The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Premier QUATRO Fire Alarm System: PRODUCT I (MA) I (MA)
  • Page 56: Standby Battery Calculation

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 15.2 STANDBY BATTERY CALCULATION In order to calculate the standby battery size required, the following formula can be used:- Battery Size (Standby time in Amp Hours) = 1.25 x [(T ) + (T x (I Where:...
  • Page 57: 16- Quatro Panels Available

    www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 16- QUATRO PANELS AVAILABLE MODEL PRODUCT CODE Premier Quatro 1 Loop Analogue Addressable Fire Alarm Panel QT/1 Premier Quatro 2 Loop Analogue Addressable Fire Alarm Panel QT/2 Premier Quatro 3 Loop Analogue Addressable Fire Alarm Panel QT/3...
  • Page 58 www.acornfiresecurity.com PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 INSTALLATION MANUAL MODIFICATION HISTORY Issue Date Changes 1.26 17/1/2011 Version before Modification history page added (Typo in date – should be 17/1/2012) 1.27 23/4/2012 Amended PSE Output voltage range (p50) Amended CIE input voltage range (p50) Reworded Port list (p50) 1.28...
  • Page 59 PREMIER QUATRO INSTALLATION MANUAL (Fyreye MKII) Firmware Versions: PANEL 1.84 & LOOP 3.70 0359 Zeta Alarm Systems, 72-78 Morfa Road, Swansea SA1 2EN 0359-CPD-0139 EN54-2:1997+A1:2002 + A2: 2006 EN54-4:1997+A1:2002 + A2: 2006 Control and indicating equipment for fire detection and fire...