Part Names
No.
Name
SIGNAL I/F
Contact signal
interface connector
Switches for
independent contact
signals
13
Outputs status information of the UPS such as a power outage or voltage drop.
External Transmission Signals and Shutdown Input Signals
Signal Name
This signal is output when there is a power outage
AC Input Error
or voltage error of the utility power supply.
Battery voltage
This signal is output when the battery voltage drops
drop
to or below the specified value (approx. 178 V).
This signal is output when AC output is being
AC output
Output
supplied to a load device.
signal
This signal is output when inverter output is being
Inverter output
supplied to a load device.
This signal is output when the utility power supply
Bypass output
is being supplied from the bypass circuit.
Device error
This signal is output when a UPS error occurs.
The UPS is shut down as a result of receiving 5 V
DC (pulse signal of at least 4 sec.) during battery
operation when there is a power outage. Current
flows at approximately 5 mA when the power is on.
Input
UPS shutdown
This is enabled when the interface is set to
signal
Standalone . For the setting procedure, see §3.5
"Setting PC Interface" in the
Manual
External Transmission Signals and Electrical Characteristics
Interface: Relay non-voltage contact signal
Contact rating: AC100V/DC50V, 0.1A
Note
When connecting an inductive/capacitive load, make sure the contact rating is not
exceeded.
Terminal Names
2
1
8
3
S1
11
15
4
S2
7
14
5
S3
12
6
S4
13
9
10
S1∼S4
Switches for independent signals (see ④)
:
Setting these switches to "OFF" makes each contact of the external transmission signals
independent.
Refer to contact interface connector ③, and set "ON" or "OFF" according to how the UPS will
be used by the customer. The switches are all set to "ON" at the time of shipment from the
factory.
External Appearance
1
2
3
4
When all of 1 to 4
are in the "ON"
state.
Function
Explanation
LCD Panel Operating
.
AC input error
COM
Battery voltage drop
COM
AC output
COM
Inverter output
Bypass output
COM
Device error
COM
UPS shutdown
Set them to "OFF" when using each contact signal as an
independent circuit.
Set them to "ON" when using each contact signal as a
common COM circuit.
Pin No. and Status
when Operating
1-8: ON
2-8: OFF
3-11: ON
4-7: ON
15-7: OFF
14-8: ON
5-12: ON
6-13: ON
9-10
External Appearance
D-sub 15-pin Female
⑧ ⑦ ⑥ ⑤ ④ ③ ② ①
⑮ ⑭ ⑬ ⑫ ⑪ ⑩ ⑨
Fixing screw M3