LMI LIQUITRON DM7000 Series Quick Start Manuals

Multi-parameter controller

Advertisement

Quick Links

LIQUITRON
The LIQUITRON
DM7000 series controller can
TM
be setup via the following 5 steps. Further details
are available in the installation and operations
manual and a series of how-to videos. These can
be found at
http://support.lmipumps.com.
STEP 1: Unpack and Mount Controller
Remove the controller from the packaging and attach
A
the included antenna
as seen in Figure #1.
Remove the black mounting bracket
of the controller and mount it using the four enclosed
C
screws
or appropriate fasteners.
Place the controller on the mounting bracket and
secure using the four enclosed screws
B
C
Figure #1
Note: The unit may also be wired (Step 2) prior to mounting.
2
4
6
DM7000 Series
Multi-Parameter Controller
to the connector on the side
B
from the back
D
.
D
A
D
STEP 2: Wire the Controller
The extent of wiring needed will depend on your
application and if your unit comes with a power cord and
pigtails. Refer to the wiring diagram below (Fig# 2) which
is also available on the inside of the controller door.
WARNING: Be sure to connect all wiring without
power applied to the controller. Failure to do so
may result in incorrect measurements.
The terminal board has the following sections:
1
Line Power: This includes input power, pump relays,
blowdown valve, and alarm relay. Wire the line, neutral,
and ground wires for each relay being used. For the
blowdown relay, ensure you wire to the normally open
and/or normally closed terminal depending upon the
type of blowdown valve connected.
2
Sensors: Use this section to connect various sensors -
pH, conductivity, ORP, temperature.
3
Flow Meters: Connections are available for makeup
and blowdown flow meters. 24 volt DC power is
available for flow meter or other device that needs
power.
4
Flow Switch: For applications that require flow
detection, wire the flow switch here after removing the
supplied jumper. Otherwise, leave the jumper in place.
5
Low Tank Sensor: Four low tank sensor connections
are available.
6
4-20 mA Outputs: Two outputs are intended for data
logging on devices such as chart recorders. Sensors
can be configured to these outputs.
7
Pulse Pacing: Two outputs may be connected for
pulse control of pumps. Pumps must be powered from
terminal board section
7
3
5
Quick Start Guide
1
.
Figure #2
1
Literature 56673 8/2018
©2018 Milton Roy, LLC
Page 1

Advertisement

loading

Summary of Contents for LMI LIQUITRON DM7000 Series

  • Page 1 Quick Start Guide LIQUITRON DM7000 Series ™ Page 1 Multi-Parameter Controller The LIQUITRON DM7000 series controller can STEP 2: Wire the Controller be setup via the following 5 steps. Further details The extent of wiring needed will depend on your are available in the installation and operations application and if your unit comes with a power cord and manual and a series of how-to videos.