Remote annunciator for use with the sxl-ex control panel, for indoor use only in dry environments

Advertisement

Lamp Test
Testing the LED-3/4 Module Lamps
To test the LEDs on the LED-3/4 module for
operation, set the address on Switch S1 as
shown below:
After testing is complete, reset Switch S1 to the
desired address setting for the module.
Enabling the Test Mode for SXL-EX
Enter level 5 of the test mode.
1. Press the RESET and DRILL keys at the
same time. The TROUBLE LED lights, and
the letter E appears on the seven segment
display.
2. Enter the password by pressing the appropri-
ate keys:
ACK = 1
RESET = 2
Then press the SILENCE key.
The seven segment display either shows F, to
indicate an incorrect password, or A, to
indicate that the password is accepted. If the
letter F appears, repeat Steps 1 and 2. If the
letter A appears, continue on to the next step.
3. Press the ACK key twice to enter the Test
Mode. The PROGRAM/TEST LED on the
front panel lights, and the seven segment
display shows the letter t.
4. Select test level 5 for the Lamp Test by
pressing the RESET key five times; then
press the SILENCE key.
Test level 5 has two sublevels:
1) Local display lamp test
2) Remote display lamp test
The sublevel is displayed on the seven segment
display following the hyphen (-). To select the
desired sublevel, press the SILENCE key as
required.
Press and hold the DRILL key to enable the
Lamp Test, and then release the DRILL key to
disable the Lamp Test.
P/N 315-093066-11
DRILL = 3
SILENCE = 4
Exiting the Test Mode
To exit the test mode, first press the ACK key until
the PROGRAM/TEST LED turns off and the letter
L appears on the seven segment display. Then
press the SILENCE key.
BATTERY CALCULATIONS
Battery backup is required for the LED-3/4. To
determine the size battery you need use the
battery calculation table in the SXL-EX Manual,
P/N 315-095997.
TROUBLESHOOTING
If an LED fails to respond:
1. Check DS17 on the back of the module for
activity. If there is no activity, it means there
is a module with possible problems, such as
incorrect address, missing or incorrect
wiring, no power at the module, or some
system problem.
2. Remove the module from its backbox to
examine the DS17 LED. Do not touch the
screw terminals to anything or damage
could result.
3. Check the control panel for proper annuncia-
tion of the alarm, supervisory, or trouble
condition.
4. Check the wiring between the module and
the control panel.
5. Check the address setting on switch S1,
which is located on the back of the module.
Remove the module from its backbox to
examine S1.
6. Check that there are 24 volts between the
TB1 terminals +24V and -V.
7. If the problem continues, replace the module.
8. Check the new module for correct wiring and
check the address settings on S1 before
powering up the system.
If Fault Code 8 appears on the SXL-EX
display:
1. The module is connected but is not configured.
Refer to the LED-3/4 Programming instructions.
2. The module is configured but is not connected.
Refer to the LED-3/4 Annunciator instructions.
3. Check the module for an error in wiring.

Advertisement