wtw TecnoLine LF 171 Operating Manual page 95

Conductivity industrial monitors
Table of Contents

Advertisement

Available languages

Available languages

Parameterization
With
set temperature limit value
(in steps of 1°C).
Setting range: -5 ... +60 °C
⇐ Relay number is displayed
With
accept and go on to
"HYST UL TEMP".
With
set hysteresis.
Setting range is ± 5°C
With
accept and go on to
"DL UL TEMP".
With
set delay time.
Setting range: 0 ... 20 seconds.
With
accept and go on to "MESSAGE
OFF / MESSAGE ON".
With
select between ON and OFF.
With
accept and go on to next menu or to
submenu "PARA TIMER"
(with timer function selected for a relay -
configuration: menu CONF RELAYS).